OM-4405 Page 53
10-3. Grounding When Supplying Building Systems
ST-800 576-B
1
Equipment Grounding
Terminal
2
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3
Ground Device
Ground generator to system
earth ground if supplying
power to a premises (home,
shop, farm) wiring system.
GND/PE
1
2
Use ground device as stated
in electrical codes.
2
3
10-4. How Much Power Does Equipment Require?
S-0623
1
Resistive Load
A light bulb is a resistive load and
requires a constant amount of pow-
er.
2
Non-Resistive Load
Equipment with a motor is a non-re-
sistive load and requires approxi-
mately six times more power while
starting the motor than when run-
ning (see Section 10-8).
3
Rating Data
Rating shows volts and amperes,
or watts required to run equipment.
VOLTS 115
4.5
60
AMPS
Hz
1
2
3
3
EXAMPLE 1: If a drill uses 4.5 amperes at 115 volts, calculate its running power
requirement in watts.
4.5 A x 115 V = 520 W
The load applied by the drill is 520 watts.
EXAMPLE 2: If three 200 watt flood lamps are used with the drill from Example 1,
add the individual loads to calculate total load.
The total load applied by the three flood lamps and drill is 1120 watts.
(200 W + 200 W + 200 W) + 520 W = 1120 W
AMPERES x VOLTS = WATTS
Summary of Contents for Big 40 WG
Page 29: ...OM 4405 Page 25 Notes...
Page 37: ...OM 4405 Page 33 SECTION 8 MAINTENANCE TROUBLESHOOTING 8 1 Maintenance Label...
Page 51: ...OM 4405 Page 47 Notes...
Page 53: ...OM 4405 Page 49 201 991 A...
Page 54: ...OM 4405 Page 50 Figure 9 2 Circuit Diagram For CC CV Welding Generator...
Page 55: ...OM 4405 Page 51 201 992 A...
Page 63: ...OM 4405 Page 59 Notes...