Vent Locations

Vented dryers
T1312, T1313

Rear View

Left Side View

Right Side View

4 3/4"

3 7/8"

4 3/4"

3 1/2" - 4 1/4"

3 1/2" - 4 1/4"

3 1/2" - 4 1/4"

Vent Locations

Vent Duct Calculations

Maximum Duct Lengths

4" diameter

65 feet

4 3/16" diameter

98 feet

4 3/4" diameter

140 feet

5" diameter

196 feet

Type of Bend or duct

Effective Radius

Subtract

Flexible duct 90°

4 - 12 inches

1 3/4 feet

Flexible duct 90°

12 - 20 inches

1 1/4 feet

Flexible duct 45°

4 - 20 inches

1 1/4 feet

Smooth duct 90° or 45°

4 - 8 inches

1 1/4 feet

Elbow 90°

Sharp bend

8 1/4 feet

Concertina bend

8 inch

2 3/4 feet

Segmented bend

8 inch

2 feet

Louvered wall or window vent (#03780400)

12 1/2 feet

Wall vent kit with flap (#00087184)

5 feet

Window vent kit with flap (#00087185)

5 feet

Exhaust connection - left

20 feet

Exhaust connection - right

33 feet

Flat duct (#01221330)

59 feet

DO NOT use vinyl ducting
with Miele appliances.

Corresponding Dryer Height with NO lid: 32 1/8" - 32 7/8"

Corresponding Dryer Height with lid: 33 3/8" - 34 1/8"

Summary of Contents for T 1322C CONDENSER DRYER

Page 1: ...ut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 240 Volt 30 Amp line to connect two Miele machines without rewiring E V 5 foot 208 240 Volt 15 Amp 4 wire 2 live neutral ground molded plug power supply connects upper right rear NEMA 14 30 Configuration Venting location may be adjusted to lower right or left side or lower l...

Page 2: ...e Cut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 240 Volt 30 Amp line to connect two Miele machines without rewiring E V 5 foot 208 240 Volt 15 Amp 4 wire 2 live neutral ground molded plug power supply connects upper right rear NEMA 14 30 Configuration Venting location may be adjusted to lower right or left side or lowe...

Page 3: ... codes See Cut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 240 Volt 30 Amp line to connect two Miele machines without rewiring E D CD 5 foot 208 240 Volt 15 Amp 4 wire 2 live neutral ground molded plug power supply connects upper right rear NEMA 14 30 Configuration Drain location Removable drawer if drain connection is n...

Page 4: ...cal codes See Cut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 240 Volt 30 Amp line to connect two Miele machines without rewiring E D CD 5 foot 208 240 Volt 15 Amp 4 wire 2 live neutral ground molded plug power supply connects upper right rear NEMA 14 30 Configuration Drain location Removable drawer if drain connection i...

Page 5: ...ance with local codes See Cut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 240 Volt 30 Amp line to connect two Miele machines without rewiring E D CD 5 foot 208 240 Volt 15 Amp 4 wire 2 live neutral ground molded plug power supply connects upper right rear NEMA 14 30 Configuration Drain location Removable drawer if drain ...

Page 6: ...ical Connection Location C 32 3 8 35 1 4 Needed depth will vary by model number T1302 T1303 T1322C T1323C 24 minimum T1329C 25 minimum Typically requires removal of unit s lid Out of box unit height dimension without lid is 32 5 16 32 11 16 Notes Location Codes C Cutout for Electric and Vent or Drain pass through Adjust according to duct or drain location ...

Page 7: ...xisting 208 240 Volt 30 Amp Product Dimensions Easy Installation Kits 057B 060B Notes Connect Washer and Dryer to Easy Installation Kit All installations must be done in accordance with local codes 057B Kit fitted with a NEMA10 30 Plug 060B Kit fitted with a NEMA14 30 Plug ...

Page 8: ...e SPECIFICATION SHEETS 010706 Product Dimensions Laundry Stand WTS420 White Only 26 11 Notes For use with both large and super capacity washers or tumble dryers All installations must be done in accordnace with local codes 23 3 8 ...

Page 9: ... rear 5 foot separate flexible hot and cold water intake hoses connect upper left rear Venting location may be adjusted to lower right or left side or lower left rear see separate sheet Location Codes Notes All installations must be done in accordance with local codes See Cut out Dimensions sheet for undercounter or built in space requirements Optional Easy Installation Kits utilize existing 208 2...

Page 10: ... installation Version 2 Custom Front Panel Width 23 3 8 for all machines Thickness up to 3 4 Height Up to 25 With this version the existing front panel is removed and replaced by the new custom panel Miele Decor Laundry unit Hinge Notches In certain installations notches will be required to accomodate the hinges in the front panel Miele Decor Laundry Control Panel To center lines 16 3 4 Notch Patt...

Page 11: ...uct 90 12 20 inches 1 1 4 feet Flexible duct 45 4 20 inches 1 1 4 feet Smooth duct 90 or 45 4 8 inches 1 1 4 feet Elbow 90 Sharp bend 8 1 4 feet Concertina bend 8 inch 2 3 4 feet Segmented bend 8 inch 2 feet Louvered wall or window vent 03780400 12 1 2 feet Wall vent kit with flap 00087184 5 feet Window vent kit with flap 00087185 5 feet Exhaust connection left 20 feet Exhaust connection right 33 ...

Page 12: ... Dryer Example Combination Rear View Left Side View Right Side View Vent Locations Corresponding Total Height with lid 66 3 8 67 1 8 4 3 4 36 3 8 37 1 8 Stacking Kit Stacking Kit 36 3 8 37 1 8 3 7 8 4 3 4 Stacking Kit 36 3 8 37 1 8 ...

Reviews: