Installation
*INSTALLATION*
45
a
Exhaust connection can be made on the top, left side and rear of the ventilation
blower box.
b
The ventilation hood is fastened in the cut-out using clamps. A solid installation
surface, e.g., made of wood, is required. Make sure that the structure can
support the load. Around the clamps, components such as supports and
ducting must be at least 1" (25 mm) from the cut-out.
c
There are additional fixing points on the installation surface.
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop, follow
the minimum safety distances between a cooktop and the bottom of the hood.
Please also observe the information contained in the “IMPORTANT SAFETY
INSTRUCTIONS” section.
Minimum distance S
Cooking appliance
Miele
appliance
Non-Miele
appliance
Electric Cooktops
24" (610 mm)
Electric Barbeques and Fryers
26" (660 mm)
Multiburner Gas Cooktops
≤
43,000 BTU/hr (12.6 kW),
no burner
>
15,000 BTU/hr (4.5 kW).
26" (660 mm)
30" (760 mm)
Multiburner Gas Cooktops
≤
73,800 BTU/hr (21.6 kW),
no burner
>
16,500 BTU/hr (4.8 kW)
30" (760 mm)
Multiburner Gas Cooktops
>
73,800 BTU/hr (21.6 kW),
or one of the burners
>
16,500 BTU/hr (4.8 kW)
Not possible
Single Burner Gas Cooktops
≤
20,500 BTU/hr (6 kW)
26" (660 mm)
30" (760 mm)
Single Burner Gas Cooktops
>
20,500 BTU/hr (6 kW)
≤
27,600 BTU/hr (8.1 kW)
30" (760 mm)
Single Burner Gas Cooktops
>
27,600 BTU/hr (8.1 kW)
Not possible