Miele professional PWT 6089 EL Installations Plan Download Page 10

Electrical 

isolator 

Both washer-dryer stack connections must be disengaged by a common electrical disconnect device 
that switches off all poles in accordance with IEC 60947-1 

[Q1]

The electrical isolator 

[Q1]

 and plug connections 

[EL1, EL2]

 must be located in the immediate vicinity 

of the machine. Both must be visible, accessible and within easy reach. 

If the electrical isolator 

[Q1] 

is not in full view of a person performing maintenance work on the machine 

at all times, the electrical isolator must be fitted with a lock. 

Installation proposals: 

Technical datasheet: PWT 6089 EL 

Date: Feb-2015 

Page: 10 

-Electrical isolator before fusing-

-Electrical isolator behind fusing-

Summary of Contents for PWT 6089 EL

Page 1: ...Installation plan Washer dryer stack PWT 6089 EL Electrically Heated en US 13 15 M Nr 10 167 290 00...

Page 2: ...tional Headquarters 9 Independence Way Princeton NJ 08540 Phone Fax www mieleusa com Technical Service Support Nationwide Phone 800 991 9380 Fax 800 220 1348 proservice mieleusa com 800 991 9380 609 4...

Page 3: ...11 3 4 11 3 4 27 1 4 76 27 1 2 14 5 8 15 1 8 52 5 8 17 3 8 43 1 4 76 30 28 5 8 27 1 4 20 7 8 50 3 4 19 1 2 12 3 4 21 1 4 30 27 1 4 43 1 4 27 1 4 27 1 2 PWT 6089 EL measurements in inches 3...

Page 4: ...51 1 8 42 1 4 39 3 8 51 1 8 5 7 8 51 1 8 39 3 8 42 1 4 43 1 4 PWT 6089 EL measurements in inches 4...

Page 5: ...76 3 4 27 1 4 28 14 24 3 4 17 3 8 22 4 43 1 4 27 1 8 1 5 8 2 1 4 PWT 6089 EL measurements in inches 5...

Page 6: ...PWT 6089 EL measurements in millimeters 6...

Page 7: ...PWT 6089 EL measurements in millimeters 7...

Page 8: ...PWT 6089 EL measurements in millimeters 8...

Page 9: ...Length of supply lead 78 2000 mm Supply lead with plug NEMA L6 30P Electrical connection must be in full compliance with national regulations and guidelines and with relevant local codes Similarly rel...

Page 10: ...EL2 must be located in the immediate vicinity of the machine Both must be visible accessible and within easy reach If the electrical isolator Q1 is not in full view of a person performing maintenance...

Page 11: ...nnector for drain hose int diameter x length 7 8 x 1 3 16 22 30 mm Max transient throughput 6 9 l min 26 l min Drain pump head height from floor level 39 3 8 1000 mm Vented drainage required If ventil...

Page 12: ...210 kg Dynamic floor load max 3600 N 3600 N Static floor load max 2850 N 2850 N Dynamic load max 750 N 750 N Drum frequency max 22 Hz 22 Hz Average heat dissipation dependent on ambient room temperatu...

Reviews: