MNTransition Instructions
7 | Page
1 0-345-1 REV C
Typical wiring diagram
It is the responsibility of the installer to verify compliance with all local and national codes.
Be certain to use UL approved wire with a voltage rating appropriate for your installation.
600 Volt wire for 600 Volt systems and 1 000 Volt wire for 1 000 volt systems.
Do not exceed 1 000 Volts.
This enclosure is not a disconnect. The disconnect must be rated for the voltage and current
applied to this transition box. The disconnect must break both PV+ and PV- on ungrounded
PV arrays. The disconnect should be located next to the inverter.
CAUTION:
On any installation that exceeds 750 Volts the installer is required to mark adjacent to each wiring compartment
"
DANGER - HIGH VOLTAGE
".