MidNite Solar MNTransition Instruction Manual Download Page 4

4 | Page

1 0-345-1 REV C

MNTransition Instructions

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

- THESE INSTRUCTIONS CONTAIN IMPORTANT SAFETY AND OPERATING INSTRUCTIONS FOR

MIDNITE SOLAR COMBINER MODEL MNTRANSITION-1 000V

If you do not fully understand any of the concepts, terminology, or hazards outlined in these instructions, please refer installation to a qualified dealer, electrician or

installer. These instructions are not meant to be a complete explanation of a renewable energy system. All installations must comply with national and local electrical

codes. Professional installation is recommended.

GENERAL PRECAUTIONS

:

WORKING WITH OR IN THE VICINITY OF A LEAD ACID BATTERY, SEALED OR VENTED IS DANGEROUS. VENTED

BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION. FOR THIS REASON, IT IS VERY

IMPORTANT THAT BEFORE SERVICING EQUIPMENT IN THE VICINITY OF LEAD-ACID BATTERIES YOU REVIEW AND

FOLLOW THESE INSTRUCTIONS CAREFULLY.

If service or repair should become necessary, contact MidNite Solar Inc. Improper servicing may result in a risk of shock, fire or explosion. To reduce

these risks, disconnect all wiring before attempting any maintenance or cleaning. Turning off the inverter will not reduce these risks. Solar modules

produce power when exposed to light. When it is not possible to disconnect the power coming from the Photovoltaics by an external means such as a

combiner, cover the modules with an opaque material before servicing any connected equipment.
Do Not expose to rain or snow. NEVER attempt to charge a frozen battery. Do not smoke around batteries.
When it is necessary to remove a battery, make sure that the battery bank disconnect breaker is in the off position and that the PV breakers, grid

breakers and any other sources of power to the inverter are in the off position. Then

remove the negative terminal from the battery first

.

To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer as well as the manufacturer of any

additional equipment used in the vicinity of the batteries.

Avoid producing sparks in the vicinity of the batteries when using vented batteries. Provide ventilation to clear the area of explosive gases. Sealed AGM

and Gel batteries do not under normal conditions create explosive gases. Refer to the battery manufacturer's documentation. Be especially cautious

when using metal tools. Dropping a metal tool onto batteries can short circuit them. The resulting spark can lead to personal injury or damage to the

equipment. Provide ventilation to outdoors from the battery compartment when installing vented batteries such as golf cart T-105 batteries. The addition

of a spill tray is also a good idea.
Clean all battery terminals. Very high currents are drawn from the batteries; even a small amount of electrical resistance can result in overheating, poor

performance, premature failure or even fire.

Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing or eyes. Wear complete eye and clothing protection. Always

avoid touching eyes while working near batteries. If battery acid or battery terminal corrosion contacts skin or clothing, wash immediately with soap and

water. If acid enters the eyes, immediately flood with cool running water for at least 15 minutes and get medical attention immediately. Baking soda

neutralizes battery acid electrolyte. Keep a supply near the batteries
Do not work alone. Someone should be in the range of your voice or close enough to come to your aid when you work with or near electrical equipment.

Remove rings, bracelets, necklaces, watches etc. when working with batteries, photovoltaic modules or other electrical equipment. Power from an

illuminated photovoltaic array makes a very effective arc welder with dire consequences if one of the welded pieces is on your person.
To reduce the risk of injury, connect only deep cycle lead acid type rechargeable batteries. Other types of batteries may leak or burst, causing personal

injury or damage.
Wiring methods used shall be in accordance with the Canadian Electrical Code, Part I.

Wiring must be done in accordance with the National Electrical Code Article 690 ANSI/NFPA 70. Use Class 1 wiring methods for field wiring connections

to terminals of a Class 2 circuit. Use only 14-10 gauge AWM wire. Select the wire gauge used based on the protection provided by the circuit

breakers/fuses. Overcurrent protection must be installed as part of the system installation. Refer to the wiring diagrams provided in

this manual for breaker/fuse/GFDI sizes and model numbers.

WARNING

:

This unit is not provided with a GFDI device. This inverter or charge controller must be used with an external GFDI device as required by

the Article 690 of the National Electrical Code for the installation location.
Use of attachments or accessories not approved by MidNite Solar could result in damage or injury.

Before making any connections verify that the circuit breakers are in the off position including the inverter breaker. Double check all wiring before

applying power.

Warnings.............................................................................................. 2

Tools Required..................................................................................... 4

Introduction.......................................................................................... 5

Cover Removal.................................................................................... 5

Wire Tightening Torque........................................................................ 5

Installation............................................................................................ 5

Dimensions and knockout location...................................................... 6

Wiring Diagram.................................................................................... 7

Table of Contents

Symbols used in this manual

Ground Symbol

Indicates an earth ground connection.

Tools required:

You will need:

#2 Phillips screwdriver

Torque screwdriver 1 /4" slotted set to 20 in-lbs (2.3 Nm) Page 5 wire tightening torque.

Drill and bit if desired for wall mount pilot holes

Wire cutters & strippers

Hammer & slotted screwdriver to remove knockouts

Silicone sealant may be used on outdoor installations to enhance weatherproofing.

Summary of Contents for MNTransition

Page 1: ...All aluminum powder coated housing that won t rust Flip up cover that can stay in the open position during installation Chassis ground bus bar 14 6 and 1 0 14 Tin plated copper bus bar to combine bre...

Page 2: ...n short circuit them The resulting spark can lead to personal injury or damage to the equipment Provide ventilation to outdoors from the battery compartment when installing vented batteries such as go...

Page 3: ...e r paration ou service d entretien consulter un agent sp cialis Il y a peut tre plusieurs sources d alimentation dans cette system D brancher toutes les interrupteurs avant toute d entretien o nettoy...

Page 4: ...ymbols used in this manual Ground Symbol Indicates an earth ground connection Tools required You will need 2 Phillips screwdriver Torque screwdriver 1 4 slotted set to 20 in lbs 2 3 Nm Page 5 wire tig...

Page 5: ...AWG 20 in lbs 2 3Nm 8AWG 25 in lbs 2 8Nm 6AWG 35 in lbs 4 0Nm 4AWG 45 in lbs 5 1Nm 2AWG 1 0 50 in lbs 5 6Nm Torque Using a torque screwdriver torque all connections to the values shown below After one...

Page 6: ...ailable on the MNTPW Note that the center bottom knock out is sized for a 1 1 4 conduit adapter The left and right side each have a knock out for either wire entry or for lightning arrestors Lightning...

Page 7: ...e for 600 Volt systems and 1000 Volt wire for 1000 volt systems Do not exceed 1000 Volts This enclosure is not a disconnect The disconnect must be rated for the voltage and current applied to this tra...