P a g e                                                                                                                 1 0 - 0 2 9 - 1           R E V   D

 

MNE-240 E-PANEL INSTRUCTIONS

 

 

 

 

 

3.11 Final Installation Tidbits: 

Wiring the Inverter Remote Control 

Refer to figure 13 for the following steps:

 

1. Connect one of the RJ11 connector ends of the remote communication cable to the back of the 

remote; refer to the ME-RC owner’s Manual for specific information.

 

 

2. Route the other RJ11 connector end through the E-Panel and E-Panel door and connect to the 

inverter’s RJ11 REMOTE PORT (blue label).

 

 

Additional Accessory Wiring

 

 

Before  attaching  the  DC  cover  to  the  inverter  end,  if  you  have  any  of  the  following  inverter 

accessories, then you will also need to route their connecting cables through the E-Panel (and 

pass through the small snap-in grommet in the door) to the RJ11 Ports on the inverter:

 

 

• Automatic Generator Start Controller (ME-AGS) for automatic generator starting an stopping.

 

 

• Battery Monitor (ME-BMK-NS) for determining your batteries State of Charge.

 

 

• Simple ON/OFF adapters (ME-RSA, ME-RSA-M) that allow the inverter to be remotely turned 

on/off.

 

 

See the appropriate accessory  owner’s guide or further information  about the installation and 

configuration of these accessories.

 

 

Installing Inverter Shield/Covers

 

 

Refer to figure 1 to identify the following components

:

 

 

Upper Shield - Attach the upper shield to the E-Panel door using three 10-32 x 3/8” machine 

screws and kepnuts.

 

 

DC Cover - Attach the DC cover using four 10-32 x 7/16” taptite screws and at least one #10 

internal tooth star washers.

 

Summary of Contents for MNE-240 Series

Page 1: ...1 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS MNE 240 240 Volt Magnum PAE E Panel Owner s Manual...

Page 2: ...parks in the vicinity of the batteries when using vented batteries Provide ventilation to clear the area of explosive gases Sealed AGM and Gel batteries do not under normal conditions create explosive...

Page 3: ...couver Pour toute r paration ou service d entretien consulter un agent sp cialis Il y a peut tre plusieurs sources d alimentation dans cette system D brancher toutes les interrupteurs avant toute d en...

Page 4: ...e AC and DC wiring bus bars and disconnects required to connect the Magnum MS PAE Series inverter charger system It also provides additional room to install additional equipment such as the MidNite Cl...

Page 5: ...round Bus bar ME BMK Battery Monitor MS PAE Series Inverter Charger 500A 50mV Shunt Charge Controller DC Cover Positive and Negative Inverter Cables Inverter AC input Output Wires Door Grommet 3 5 Low...

Page 6: ...our installation Info Installations should be performed by qualified personnel such as a licensed or certified electrician It is the installer s responsibility to determine which safety codes apply an...

Page 7: ...7 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS Figure 2 MNE 240 Series E Panel System Wiring Diagram...

Page 8: ...UIT KNOCKOUTS ARE MIRROR IMAGE OF BOTTOM KNOCKOUTS 4 67 12 90 22 37 0 75 17 00 4 17 INSIDE 1 13 3 4 CONDUIT INSIDE 1 38 1 CONDUIT 24 91 26 45 INSIDE 0 87 1 2 CONDUIT INSIDE 2 47 2 CONDUIT 25 55 0 87 1...

Page 9: ...ons after an hour and also conduct a pull test You may be surprised that what you thought was a tight connection actually pulls out with little effort Copper is a relatively soft metal and will contin...

Page 10: ...bustible fluid or components i e paper cloth plastic etc that may be ignited by heat sparks or flames they must be at a minimum distance of 2 feet away from the E Panel inverter his E Panel system wil...

Page 11: ...ol P WR FA U LT C H G I N V SELE CT C H A R G ER Magnum Inverter Charger MidNite Solar Classic Controller MNE 240 Series E Panel I NV E RTER S HO RE AG S M E TE R S E T UP TEC H Bottom Mounting Bracke...

Page 12: ...h E Panel Mounted Figure 8 Securing the Inverter to the E Panel Door As shown in figure 8 secure the inverter to the E Panel door using six 6 mm x 20 mm taptite thread forming pan head Phillips screws...

Page 13: ...to the wiring terminals All wiring within the E Panel enclosure except low voltage control wiring shall be rated at least 250V or a combination of 250V e g 125V cable enclosed in 125V insulation heat...

Page 14: ...tion DC CONNECTIONS DC CONNECTIONS E Panel with Left Hand Door E Panel with Right Hand Door Figure 12 E Panel Wiring Connections AC Wiring Connections The AC Bus Bars for neutral and hot connections h...

Page 15: ...negative and positive terminals before turning ON the DC battery breaker or damage will occur The inverter s warranty doesn t cover repair to the inverter from this damage Caution The battery bank vol...

Page 16: ...onnect to inverter DC Negative from shunt to inverter Wire Grommet snapped into door DC Ground from battery to E Panel from battery to disconnect Battery Temp Sensor from battery to inverter 12V 12V B...

Page 17: ...1 and AC HOT IN 2 bus bars in the E Panel respectively 2 Route a wire from the neutral bus bar in the main panel and connect to the NEUTRAL bus bar in the E Panel 3 Route a wire from the ground bus ba...

Page 18: ...F F Main Panel Utility Generator Input ON OFF AC Output Wiring AC Input Wiring 120 240VAC from Main Panel to AC HOT IN and NEUTRAL Bus bars AC Output Wiring a Wire to an electrical sub panel or b Use...

Page 19: ...N O F F I N VERTER SHO R E A G S M E TE R SE TU P TE C H ME RC ME ARC Remote Control GROUND MS PAE Series Inverter Charger 3 5 Wire Grommet snapped into door AC Inverter wires pre wired in the E Pane...

Page 20: ...heir connecting cables through the E Panel and pass through the small snap in grommet in the door to the RJ11 Ports on the inverter Automatic Generator Start Controller ME AGS for automatic generator...

Page 21: ...tage should be 240 Vac 3 B Testing the E Panel AC Input Output Wiring 1 If the Inverter AC output voltages are correct tested above a turn the inverter OFF b slide the Inverter Bypass switch to the BY...

Page 22: ...3 120VAC 3 120VAC 3 120VAC 3 240VAC 3 240VAC 3 E Panel with Left Hand Door E Panel with Right Hand Door B Testing the E Panel AC Input Output wiring Inverter is OFF Utility or Generator power to E Pan...

Page 23: ...erter turned off the inverter the connected loads or any other installed equipment beyond the E Panel can be serviced Inverter Bypass Switch The Inverter Bypass Switch allows the incoming AC power uti...

Page 24: ...the Bypass mode the power from the utility or generator routes through the Inverter Bypass Switch directly to the sub panel This mode allows the AC power to bypass the inverter and continue powering...

Page 25: ...8223 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any defective MidNite Solar product under this warranty policy Except for the warranty that the products are m...

Reviews: