Hawke’s Bay
Manual
13| P a g e 1 0 - 4 2 5 - 1 R E V : - F W : X X X
Terminal Block #4 -
AUX 1 and AUX 2 circuits; Battery Voltage Sense circuit; and Whiz Bang Jr,
current-sense device. Use
#22 AWG
wire.
Terminal Block #5 -
Connect the DC input (PV) wires and the Battery Bank wires here. From
left-to-right: PV+ / PV- / Batt - / Batt+. Accepts up to
#2 AWG
wire.
Ground Wire Lug (Figure 3) -
Use
#6 AWG
wire for
grounding electrode conductor.
Options Board (Figures 4 & 5)
The Options Board is an installed circuit card that allows
for the connection of Arc Fault, Ground Fault, and Rapid
Shutdown System sensors (toroids).
Figure 4
shows the location of the Option Board
installed in the
Hawke’s Bay
.
Figure 5
shows the Options Board, sub-boards, and
connection receptacles.
Bypass Switch & TB1 (Figure 5)
For Rapid Shutdown System operations, the Hawke’s
Bay via the Options Board can be configured to accept an external switch to initiate Rapid
Shutdown.
On the lower right corner of the Options
Board is a Bypass Switch (CON4). To
allow an external switch to control RSS,
move the jumper to the JP2 position and
connect the wires from the external
switch into the RS Switch (TB1). TB1 is
Normally Closed (NC); NC means no Rapid
Shutdown. When the input to TB1
becomes open, Rapid Shutdown is
initiated. For internal MPPT initiation of
Rapid Shutdown, move the jumper to the
JP1 position.
Figure 4
RSS Board
AF/GF
Board
Bypass
Switch
TB1
Arc Fault
Rapid
Shutdown
Ground
Fault
Figure 5
Figure 3