V4+R VRF 50/60Hz
201608
69
P
art
5
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
4.11
H7 Troubleshooting
Digital display output
4.11.1
Description
4.11.2
Number of indoor units detected by master unit not same as number set on main PCB.
All units stop running.
Error code is only displayed on the master unit.
Possible causes
4.11.3
Number of indoor units set on main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Main PCB damaged.