V4+R VRF 50/60Hz
201608
45
P
art
5
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
Table 5-2.1: Main PCB ports
Label in
Figure 5-2.1
Port
code
Content
Port voltage
1
CN10
Compressor top temperature sensor (single compressor units) or
compressor A compressor top temperature sensor (dual
compressor units) connection
0-5V DC (varying)
2
CN11
Discharge pipe temperature sensor (single compressor units) or
compressor B compressor top temperature sensor (dual
compressor units) connection
0-5V DC (varying)
3
CN4
Inverter module temperature sensor connection
0-5V DC (varying)
4
CN26
Reserved
5
CN25
Communication port
2.5-2.7V DC
6
CN30
Power input
380V
7
CN80
Reserved
8
CN31
No.1 transformer power input
220V
9
CN33
No.2 transformer power input
220V
10
CN66
Power supply to compressor A crankcase heater
220V
11
CN67
Power supply to compressor B crankcase heater
220V
12
CN70
EVXA drive port
First pin on the left: 12V DC; other four pins:
varying
13
CN71
EVXB drive port
14
CN47-
CN49
Four-way valve drive ports
220V
15
CN41-
CN45
Solenoid valve drive ports
220V
16
CN54
Power output
220V
17
CN57-
CN59
Neutral terminals
0
18
CN32
No.1 transformer power output
Voltage between upper two pins: 13.5V AC;
voltage between lower two pins: 9V AC
19
CN34
No.2 transformer power output
Voltage between upper two pins: 14.5V AC;
voltage between lower two pins: 14.5V AC
20
CN39
Inverter module B control port
Third pin on the left: 3.3V DC
21
CN38
Inverter module B voltage monitor port
540V DC, +15V DC, N
22
CN36
Inverter module A voltage monitor port
540V DC, +15V DC, N
23
CN37
Inverter module A control port
Third pin on the left: 3.3V DC
24
CN35
5V DC, 12V DC power input
GND, +5V, +12V, GND, 12V
25
CN19
Low pressure switch connection
0 or 5V
26
CN18
High pressure switch and discharge temperature switch(es)
connections
0 or 5V
27
CN28
Reserved
28
CN16
Reserved
29
CN15
Inverter compressor A and B current sensor connections
0-7.8V AC (varying)
30
CN17
High pressure sensor connection
0-5V DC (varying)
31
CN2
Right condenser temperature detection port
0-5V DC (varying)
32
CN1
Outdoor ambient temperature sensor and outdoor heat exchanger
temperature sensor connections
0-5V DC (varying)
33
CN20
Outdoor units communication port
2.5-2.7V DC
34
CN65
Fan B control port
First pin on the left: 12V DC; other four pins:
varying
35
CN64
Fan A control port
Summary of Contents for V4+R Series
Page 2: ......
Page 4: ...V4 R VRF 50 60Hz 2 201608 Midea V4 R Series Service Manual ...
Page 103: ......