background image

GD  Midea  Refrigerant  Equipment  Co.  Ltd                                          Service  manual  for  E1  Window 

4.  Connect  the  drain  hose  to  the  outlet located  at  the  bottom  of the  drain  pan.  You  can 

purchase the drain hose or tubing locally to satisfy our particular needs (Drain hose is 

n

o

s

u

p

p

li

e

d). 

 

 

 

 

 

 

 

 

 

 

2.4  HOW TO INSTALL 

2.4.1 

Installation of the housing

 

Step 1

 

Remove the air conditioner from it's packaging, remove fixing screws and  slide the air 

conditioner out of it's housing (Refer to Installation Steps). 

Step 2 

Prepare the hole in the wall so that the bottom of the housing is well supported, the top 

has  minimum  clearance  and  the  air  inlet  louvers  have  clearance  as  shown  below  in 

options    A and B. Holes from the outside through to the cavity should be sealed. The 

housing should slope down towards the rear b about 5mm to allow water formed during 

operation to drain. 

Step 3 

Install the  housing into  the  wall  and  secure.  Ensure  the foam  seals  are  not  damaged. 

Flash, seal or fill gaps around the inside and outside to provide satisfactory appearance 

and protection against the weather, insects and rodents. 

Summary of Contents for MWF-07CM

Page 1: ...ideaaircon com Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL MODELS MWF 07CM MWF 09CM MWF 12CM MWF 16CM MWF 18CM MWF...

Page 2: ...The refrigerant is charged at the factor Be sure to read the safety precautions prior to servicing the unit 1 1 SAFET PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplug the p...

Page 3: ...motor will operate and begin auto louver function When the switch is off the louver motor will stop THERMOSTAT Set the temperature desired SELECTOR Select the operation function in COOL HEAT or FAN ON...

Page 4: ...d must be connected to an independent circuit The yellow green wire must be grounded 2 2 CHECK OF INSTALLATION The setting conditions must be checked prior to initial starting The under mentioned item...

Page 5: ...housing Refer to Installation Steps Step 2 Prepare the hole in the wall so that the bottom of the housing is well supported the top has minimum clearance and the air inlet louvers have clearance as s...

Page 6: ...the power and position excess cord length beneath the air conditioner base 3 Engage the chassis fixing brackets into the bottom housing rail and secure to the base with the screw provided 4 Remove th...

Page 7: ...ame See Fig 4 Step 3 Installation 1 Remove the two fixing screws on the chassis fixing brackets then remove the chassis fixing brackets See Fig 5 2 Grasp the handle on the chassis and carefully slide...

Page 8: ...front panel on the frame s buckle then press the front panel into the frame s slot until you hear a click See Fig10 3 TROUBLESHOOTING GUIDE 3 1 REFRIGERATION CCLE DIAGRAM The figure below is a brief...

Page 9: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 8...

Page 10: ...Test capacitor Replace if not within 10 of manufacture s rating Replace if shorted open or damaged Fan motor will not run Will not rotate Fan blade hitting shroud or blower hitting scroll Realign asse...

Page 11: ...produce high pressure and low pressure Replace the compressor after checking for the reason Heat sources Reduce if too many reverse valve The seal in valve is damaged making the low pressure connecte...

Page 12: ...ng Replace if shorted open or damaged Thermostat Check the thermostat setting if not at the coolest in cooling mode or the warmest in heating mode Set it if not Compressor will not run while fan motor...

Page 13: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 12 4 2 For models MWF 12CM 4 3 For models MWF 16CM...

Page 14: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 13 4 4 For models MWF 18CM...

Page 15: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 14 4 5 For models MWF 21CM MWF 24CM 5 EXPLODED VIEWS See attached files 6 SPECIFICATIONS See attached files...

Reviews: