GD  Midea  Refrigerant  Equipment  Co.  Ltd                                          Service  manual  for  E1  Window 

3.2 TROUBLESHOOTING GUIDE 

In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from 

an electrical defect, another is ineffective Air Conditioning caused b a defect in the refrigeration circuit and 

improper application, and the other is called the Structure Damage. 

 

ROOM AIRCONDITIONER VOLTAGE LIMITS: 

NAMEPLATE RATING 

MINIMUM 

MAXIMUM 

220~240V 

196V 

253V 

 

 

PROBLEM

 

POSSIBLE CAUSE

 

REMED

 

No power 

Check voltage at electrical outlet. Correct if none. 

Power supply cord 

Check voltage at the power cord terminal. Replace the 

power cord if none. 

Wire disconnected or 

connection loose 

Connect wire. Refer to wiring diagram for terminal 

identification. Repair or replace loose terminal. 

Main switch failure 

Check and replace the main switch if failure. 

Capacitor (Discharge 

capacitor before 

testing) 

Test capacitor.                                                                                                 

Replace if not /-10% of manufacture's rating. 

Replace if shorted, open or damaged. 

Fan motor will not 

run. 

Will not rotate 

Fan blade hitting shroud or blower hitting scroll. Realign 

assembly.                                                                                                                                                                                                 

Check fan motor bearings. Replace the motor if motor shaft 

do not rotate. 

Check voltage. Call an electrician if not within limits. 

Test capacitor.                                                                                                                                                                                         

Replace if not /-10% of manufacture's rating. 

Check bearings. Replace the motor if the fan blade cannot 

rotate freely. 

Fan motor runs 

intermittently 

Cycles on overload. 

Pay attention to any change from high speed to low speed. 

Replace the motor if the speed does not change. 

Fan 

Replace the fan if cracked, out of balance, or partially 

missing. 

Blower 

Replace the blower if cracked, out of balance, or partially 

missing. 

Loose screws 

Tighten them. 

Fan motor noise. 

Worn bearings 

Replace the motor if knocking sounds continue when running 

or loose, or the motor hums or noise appears to be internal 

while running. 

The compressor 

not to stop even 

the room 

temperature has 

got to the setting 

temperature. 

Thermostat 

Check and replace if the thermostat is damaged. 

Summary of Contents for MWF-07CM

Page 1: ...ideaaircon com Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL MODELS MWF 07CM MWF 09CM MWF 12CM MWF 16CM MWF 18CM MWF...

Page 2: ...The refrigerant is charged at the factor Be sure to read the safety precautions prior to servicing the unit 1 1 SAFET PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplug the p...

Page 3: ...motor will operate and begin auto louver function When the switch is off the louver motor will stop THERMOSTAT Set the temperature desired SELECTOR Select the operation function in COOL HEAT or FAN ON...

Page 4: ...d must be connected to an independent circuit The yellow green wire must be grounded 2 2 CHECK OF INSTALLATION The setting conditions must be checked prior to initial starting The under mentioned item...

Page 5: ...housing Refer to Installation Steps Step 2 Prepare the hole in the wall so that the bottom of the housing is well supported the top has minimum clearance and the air inlet louvers have clearance as s...

Page 6: ...the power and position excess cord length beneath the air conditioner base 3 Engage the chassis fixing brackets into the bottom housing rail and secure to the base with the screw provided 4 Remove th...

Page 7: ...ame See Fig 4 Step 3 Installation 1 Remove the two fixing screws on the chassis fixing brackets then remove the chassis fixing brackets See Fig 5 2 Grasp the handle on the chassis and carefully slide...

Page 8: ...front panel on the frame s buckle then press the front panel into the frame s slot until you hear a click See Fig10 3 TROUBLESHOOTING GUIDE 3 1 REFRIGERATION CCLE DIAGRAM The figure below is a brief...

Page 9: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 8...

Page 10: ...Test capacitor Replace if not within 10 of manufacture s rating Replace if shorted open or damaged Fan motor will not run Will not rotate Fan blade hitting shroud or blower hitting scroll Realign asse...

Page 11: ...produce high pressure and low pressure Replace the compressor after checking for the reason Heat sources Reduce if too many reverse valve The seal in valve is damaged making the low pressure connecte...

Page 12: ...ng Replace if shorted open or damaged Thermostat Check the thermostat setting if not at the coolest in cooling mode or the warmest in heating mode Set it if not Compressor will not run while fan motor...

Page 13: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 12 4 2 For models MWF 12CM 4 3 For models MWF 16CM...

Page 14: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 13 4 4 For models MWF 18CM...

Page 15: ...GD Midea Refrigerant Equipment Co Ltd Service manual for E1 Window 14 4 5 For models MWF 21CM MWF 24CM 5 EXPLODED VIEWS See attached files 6 SPECIFICATIONS See attached files...

Reviews: