95
Remark:
Use a multimeter to test the DC
voltage between 2 port and 3 port of
outdoor unit. The red pin of
multimeter connects with 2 port while
the black pin is for 3 port.
When AC is normal running, the
voltage will move alternately between
-50V to 50V.
If the outdoor unit has malfunction,
the voltage will move alternately with
positive value.
While if the indoor unit has
malfunction, the voltage will be a
certain value.
Remark,
The old label is L1,L2,S, L1,L2
The new label is 1, 2, 3, L1,L2
Remark:
Use a multimeter to test the
resistance of the reactor which does
not connect with capacitor.
The normal value should be around
zero ohm. Otherwise, the reactor
must have malfunction and need to
be replaced.
Summary of Contents for MUE-48HRFN1-M
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 9: ...6 Duct Units...
Page 10: ...7 Console...
Page 11: ...8 Ceiling floor Units...
Page 30: ...27 Console Unit Ceiling floor Units...
Page 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Page 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Page 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Page 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Page 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Page 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Page 41: ...38 MOD30U 36HFN1 M...
Page 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 61: ...58 12 Field Wiring 36K 48K...
Page 106: ...103 P U P V...
Page 107: ...104 P W P N...
Page 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...