Outdoor ambient temp.(T4)
will show “
-
9”.If the temp. is higher than 70 degree, the
digital display tube will show “70”. If the indoor unit is not
connected, the digital display tube will show: “――”
09
Compressor discharge temp.(T5)
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show
“13”.If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “0.5”,it means the compressor
discharge temp. is 105 degree. the digital display tube show
“1.6”,it means the compressor discharge temp. is 116
degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will
show single digit and tens digit.
For example, the
digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
15
Frequency limit symbol
Bit7
Frequency limit caused by
IGBT radiator
The display value is
hex number. For
example, the digital
display tube show
2A,
then
Bit5=1,
Bit3=1, Bit1=1.
It means frequency
limit caused by T4,
T3 and current.
Bit6
Frequency limit caused by
PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by
current
Bit0
Frequency limit caused by
voltage
16
DC fan motor speed
17
IGBT radiator temp.
The display value is between 30~120 degree. If the temp. is
lower than 30 degree, the digital display tube will show
“30”.If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “0.5”,it means the IGBT radiator
temp. is 105 degree. the digital display tube sh
ow “1.6”,it
means the IGBT radiator temp. is 116 degree)
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
General:1, Twins:2
19
Evaporator pipe temp. T2 of 1# indoor unit
If the temp. is lower than 0 degree, the digital display tube
will show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not
20
Evaporator pipe temp. T2 of 2# indoor unit
21
Evaporator pipe temp. T2 of 3# indoor unit
Summary of Contents for MUE-48HRFN1-M
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 9: ...6 Duct Units...
Page 10: ...7 Console...
Page 11: ...8 Ceiling floor Units...
Page 30: ...27 Console Unit Ceiling floor Units...
Page 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Page 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Page 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Page 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Page 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Page 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Page 41: ...38 MOD30U 36HFN1 M...
Page 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 61: ...58 12 Field Wiring 36K 48K...
Page 106: ...103 P U P V...
Page 107: ...104 P W P N...
Page 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...