42
For 18k and 24k models:
Compressor
on
off
on
on
on
off
off
off
4-way valve
Outdoor fan
Indoor fan
Indoor fan breeze(10s)
xx
no longer than 10m
Frequency F8
30s
10s
10s
Frequency F2
XX=90.
9.4.3.5
Evaporator
coil
temperature
protection
----T2> TEH2
℃
, the compressor running
frequency decreases to the lower level and
runs for 20s.
When the frequency decreases to F2 and the
T2 is still over TEH2
℃
for 3 minutes, the
compressor will stop.
----T2<48
℃
or T2 stays in 48
℃
~ TEH2
℃
for 6
minutes, the frequency will not be limited by T2.
----T2>60
℃
, the compressor will stop and
restart when T2<48
℃
.
9.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17~30
℃
.
In auto mode, the machine will choose cooling,
heating or fan-
only mode according to ΔT (ΔT
=T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-
1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for 15 minutes and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
9.4.5 Drying mode
9.4.5.1 Indoor fan speed is fixed at breeze
and can’t be changed. The louver angle is the
same as in cooling mode.
9.4.5.2 Compressor running rules
2.0
1.5
1.0
F3
F2
F1
F1
2.5
0.5
0.0
9.4.5.3 Low indoor room temperature protection
In drying mode, if room temperature is lower
than 10
℃
, the compressor will stop and not
resume until room temperature exceeds 12
℃
.
9.4.5.4 Evaporator anti-freezing protection,
condenser high temperature protection and
outdoor unit frequency limit are active and the
same as that in cooling mode.
9.4.5.5 The outdoor fan operates the same as
in cooling mode.
9.4.6 Forced operation function
9.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch
button will carry the machine to forced auto
mode. If pressing the button once again within
5 seconds, the machine will turn into forced
cooling mode.
In forced auto, forced cooling or any other
operation mode, pressing touch button will turn
off the machine.
9.4.6.2 In forced operation mode, all general
Summary of Contents for MSV1-09HRFN1-MT0W
Page 20: ...16 6 Wiring Diagram 6 1 Indoor Unit MSV1 09HRFN1 MT0W MSV1 12HRFN1 MT0W...
Page 21: ...17 MSV1 12HRDN1 MQ0W...
Page 22: ...18 MSV1 18HRDN1 MQ0W MSV1 24HRDN1 MQ0W...
Page 23: ...19 6 2 Outdoor Unit MOC 09HFN1 MTOW MOC 12HFN1 MTOW...
Page 24: ...20 MOC 12HDN1 MQ0W...
Page 25: ...21 MOC 12HDN1 MQ0W with low ambient temp cooling function...
Page 26: ...22 MOF 18HDN1 MQ0W...
Page 27: ...23 MOF 18HDN1 MQ0W with low ambient temp cooling function...
Page 28: ...24 MOG 24HDN1 MQOW...
Page 29: ...25 MOG 24HDN1 MQOW with low ambient temp cooling function...
Page 30: ...26 MOC 09HFN1 MTOW MOC 12HFN1 MTOW...
Page 31: ...27 MOC 12HDN1 MQ0W...
Page 32: ...28 MOF 18HDN1 MQ0W MOG 24HDN1 MQOW...
Page 60: ...56...
Page 63: ...59 P U P V...
Page 64: ...60 P W P N...
Page 90: ...86 16 2 Capacitor clip 1 201200100002 35 Electric heater of chassis 1 202403100187...