Service manual
- 6 -
4. Specification
MSG-24CRN2
MSG-24HRN2
Ph-V-Hz
1, 220-240V~,50Hz
1, 220-240V~,50Hz
Capacity
Btu/h
23000
23000
Input
W
2650
2650
Rated current
A
12.1
12.1
EER
Btu/w.h
8.7, 2.54
8.7, 2.54
Capacity
Btu/h
-----
26000
Input
W
-----
2570
Rated current
A
-----
11.7
COP
W/W
-----
2.96
A
16
16
A
54
54
Model
PG420X3CS-4KU1
PG420X3CS-4KU1
Type
Rotary
Rotary
Brand
GD Toshiba
GD Toshiba
Capacity
Btu/h
23400
23400
Input
W
2317
2317
Rated current(RLA)
A
10.1
10.1
Locked rotor Amp(LRA)
A
54
54
Thermal protector
Internal
Internal
Capacitor
uF
50
50
Refrigerant oil
ml
950
950
Model
YDK36-4G
YDK36-4G
Brand
Welling
Welling
Input
W
65/64/62
65/64/62
Capacitor
uF
2
μ
F/450V
2
μ
F/450V
Speed(hi/mi/lo) r/min
1050/960/860
1050/960/860
m3/h
1050/950/850
1050/950/850
dB(A)
43/40/37
43/40/37
Model
YDK53-6K
YDK53-6K
Brand
Welling
Welling
Input
W
140
140
Capacitor
uF
3.5
3.5
Speed
r/min
800
800
m
3
/h
2500
2500
dB(A)
55
55
g
R22/1850
R22/1900
MPa
2.8
2.8
Liquid side/ Gas side
mm
Ф
9.53/
Ф
16.0
Ф
9.53/
Ф
16.0
Max. refrigerant pipe length
m
20
20
Max. difference in level
m
10
10
℃
17-30
17-30
℃
18-45
-7 - 45
m
2
40~56
40~56
Operation temp
Ambient temp
Application area
Outdoor noise level
Refrigerant type R407C
Design pressure
Refrigerant
piping
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Outdoor
fan motor
Outdoor air flow
Max. current
Starting current
Compressor
Indoor
fan motor
Model
Power supply
Cooling
Heating
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat
different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Summary of Contents for MSG-24CRN2
Page 1: ...MSG 24CRN2 MSG 24HRN2 MSG 30CRN2 MSG 30HRN2...
Page 2: ......
Page 13: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Page 15: ...Service manual 11 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Page 16: ...Service manual 12 7 2 Wiring diagram 7 2 1 Cooling mode MSG 24CR MSG 30CR...
Page 17: ...Service manual 13 7 2 2 Heating mode MSG 24HR MSG 30HR A1 A2...
Page 18: ...Service manual 14 7 2 3 Cooling mode 3 Ph MSG 30CR 3ph...
Page 19: ...Service manual 15 7 2 4 Heating mode 3 Ph MSG 30HR 3ph 1 7 3 4 5 6 2...