60Hz R410A ClimaMaster Tropical Rooftop Package Unit MCAC-RTSM-2015-01
34
9. Performance Data
9.1 Cooling capacity for 5Ton:
Am
b
ien
t
T
e
m
p
era
ture
(
℉
)
Air Flow
CFM
1800
Ent DB
(
℉
)
75
80
85
90
75
E
n
te
ri
n
g
W
e
t
B
u
lb
(
℉
)
61
TGC
63.6
66.8
72.8
75
SHC
46.8
48.1
51.7
53.2
67
TGC
65.7
69
74.5
76.7
SHC
47.3
49
52.9
54.5
73
TGC
67.4
70.7
76.4
78.3
SHC
47.8
50.2
54.2
55.7
85
61
TGC
59.6
62.6
68.2
70.3
SHC
42.9
45.1
49.1
50.6
67
TGC
61.5
64.6
69.7
71.8
SHC
44.3
46.5
50.2
51.7
73
TGC
63
66.2
71.5
73.3
SHC
45.4
47.7
51.5
52.8
95
61
TGC
55.5
58.3
63
64.8
SHC
41.1
43.1
46.6
48
67
TGC
57.1
60
65
66.9
SHC
41.7
44
47.2
48.8
73
TGC
58.7
61.7
66.6
68.3
SHC
42.9
45
48.6
49.8
105
61
TGC
51.6
54.2
59
60.8
SHC
39.7
41.7
45.5
46.8
67
TGC
53.2
55.9
60.3
62.2
SHC
40.4
42.5
45.9
47.2
73
TGC
54.6
57.3
61.9
63.4
SHC
40.9
43
46.4
47.6
115
61
TGC
47.4
49.7
54.2
55.8
SHC
38.8
39.3
42.8
44.1
67
TGC
48.8
51.2
55.7
57.4
SHC
39
39.8
43.7
45.4
73
TGC
49.9
52.4
57.1
58.6
SHC
39.4
41.4
45.1
46.2
Notes:
1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit:1000Btu/h).
3. SHC=Sensible Heat Capacity. (Unit: 1000Btu/h).
Summary of Contents for MRBT-062CWN1-D
Page 20: ...MCAC RTSM 2015 01 60Hz R410A ClimaMaster Tropical Rooftop Package Unit 19 7 2 6 2 7 5ton ...
Page 21: ...60Hz R410A ClimaMaster Tropical Rooftop Package Unit MCAC RTSM 2015 01 20 7 3 8 5 10ton ...
Page 23: ...60Hz R410A ClimaMaster Tropical Rooftop Package Unit MCAC RTSM 2015 01 22 7 5 15 17 5ton ...
Page 24: ...MCAC RTSM 2015 01 60Hz R410A ClimaMaster Tropical Rooftop Package Unit 23 7 6 20ton ...