background image

Trouble shooting 

29

 

Capillary tube 

Regulate the flow if capillary tube and make the 
evaporating temperature appropriate if the evaporator is 
frosted. Replace if blocked. Repair joint if leaking. 

Compressor 

The inlet and outlet valve of the compressor is damaged, 
making the low pressure connected with the high pressure. 
The refrigerating system can not produce high pressure 
and low pressure. Replace the compressor after checking 
for the reason. 

Heat sources 

Reduce if too many. 

No cooling or 
heating. 

No power 

Check the voltage. Call an electrician if no within the limit. 

Wiring 

Check the terminals. Repair and correct if loose. 

Temperature setting 

Check and adjust the temperature setting. 

Mode setting 

Check and adjust the mode setting. 

Compressor 

Check and replace if the compressor, the over-load 
protector or wiring is broken. 

Electric heater failure 

Check and replace if the heater is damaged. 

Over heat fuse failure 

Check and replace if the fuse is damaged. 

Main PCB 

Check the voltage of main PCB. Replace the main PCB 
when the unit failure in heating mode. 

The unit starts 
and stops 
frequently. 

Power supply 

The input power supply voltage is too low. Call an 
electrician if not within limits. 

Main PCB 

Check and replace the main PCB if the compressor relay 
on PCB is shorted or damaged. 

Room temperature 

When the room temperature is too high, the compressor 
will protect. 

 
 

Summary of Contents for MPM1-10CEN1-BB6

Page 1: ...Portable air conditioner MPM1 10CEN1 BB6 MPM1 10EEN1 BB6 MPM1 10CRN1 BB6 MPM1 10ERN1 BB6...

Page 2: ...Permanent installation 12 7 Feature 14 8 Electronic function 15 8 1 Terms and definitions 15 8 2 Electric part assembly condition that use 15 8 3 PCB working environment 15 8 4 Protection function 16...

Page 3: ...ect the power supply plug or turn off the breaker 1 2 Caution Always check for gas refrigerant leakage after installation or repair of product Install the drain hose to ensure that water is drained aw...

Page 4: ...pe Do not mix old and mew batteries or different types of batteries Do not recharge or disassemble the batteries Do not dispose of batteries in a fire If the liquid from the batteries gets onto your s...

Page 5: ...g W H D mm 725 875 460 725 875 460 Net Gross weight Kg 40 52 40 52 Applicable ambient Operation temp 17 30 17 30 Ambient temp 10 35 35 Application area m2 14 21 14 21 Water Pump 1 and 2 Current mA 40...

Page 6: ...Number of circuits 2 2 Cond a Number of rows 2 2 b Tube pitch a x row pitch b mm 21X13 37 21X13 37 c Fin spacing mm 1 3 1 3 d Fin type code Hydrophilic aluminum Hydrophilic aluminum e Tube outside di...

Page 7: ...Outer dimension 5 3 Out dimension...

Page 8: ...External view part display 6 4 Display 4 1 LED display 4 2 LCD display...

Page 9: ...Refrigerant cycle diagram 7 5 Refrigerant cycle diagram The figure below is a brief description of the important components and their function in what is called the refrigeration system...

Page 10: ...Installation detail 8 6 PCB drawing wiring diagram 6 1 10K Model The below picture is fit for MPM1 10CEN1 BB6 MPM1 10CRN1 BB6 MPM1 10EEN1 BB6 MPM1 10ERN1 BB6...

Page 11: ...d be kept The appliance shall not be used in the washroom The plug shall accessible after appliance is positioned Wiring shall be done according to National rules Please see the picture show as below...

Page 12: ...djustable panel if the width of window is less than 26 Open the window sash and place the window panel on the window stool Secure the window panel to the window stool with 2 screws 6 4 3 Cut the foam...

Page 13: ...Adjust the length of the sliding window panel according to the width of window short the adjustable panel if the width of window is less than 26 Open the sliding sash and place the window panel on the...

Page 14: ...ter window sash Show as below picture 6 6 Permanent installation 6 6 1 Attach one end of the duct to the exhaust air outlet of the mobile air conditioner According to the arrow direction push it downw...

Page 15: ...Installation detail 13 6 6 4 Cover the hole using the adaptor cap when not in use...

Page 16: ...display LCD optional 3600 air out grille Flat plane design Sliver spray 8 meters remote controller Turbo cooling function Flexible air exhaust Advanced shower system 24 hour on off Cooling Dry Fan on...

Page 17: ...2 2 Working environment 10 C 50 C 8 2 3 The humidity of electric part working environment RH10 RH95 8 2 4 The electric storage working temperature 20 C 70 C 8 3 PCB working environment 8 3 1 Toleranc...

Page 18: ...ect the indoor evaporator from freezing Compressor will restart again when the indoor evaporator temperature rises to 10 C See the below graph At the anti freezing control the pump 1 and pump 2 mainta...

Page 19: ...arge of drain water out start to work drain the water to the auxiliary tank If the water level drops below WL1 the pump 2 stop and the outer fan motor maintain the low fan At the above 2 steps if the...

Page 20: ...t the compressor will work 5 minutes at least for each start up If the TS changed during this period judge TS and TA at once the 5 minutes wait will be cancel 8 5 5 If shutdown unit at cooling mode th...

Page 21: ...lay shows the ambient temperature at fan mode the temperature can not be adjusted 8 7 3 The fan speed can by changed at fan mode the auto fan mode function is same as the fan speed control on auto mod...

Page 22: ...different between TA and TS 8 9 5 2 If the fan motor is at low speed and TA TS 1 C the fan motor turn to middle fan and continue running 1 minute at least 8 9 5 3 If the fan motor is at middle speed...

Page 23: ...eplace compressor Terminal R and S no continuity Open winding replace compressor 9 1 2 Ground test Use an ohmmeter set on its highest scale Touch one lead to the compressor body clean point of contact...

Page 24: ...efore attempting to test 3 Apply ohmmeter probes to terminals on overload wires There should be continuity through the overload 9 1 6 Terminal overload internal Some model compressors are equipped wit...

Page 25: ...below pinch off on the suction side of the compressor Connect the line from the nitrogen tank to the suction process tube Drift dry nitrogen through the system and unsolder the more distant connectio...

Page 26: ...essors The terminal markings are on the cover gasket Use your wiring diagram to insure correct connections 9 2 6 Refrigerant charge The refrigerant charge is extremely critical It must be measured cha...

Page 27: ...is marked with a red dot and is wired to the line side of the circuit 9 4 1 Capacitor test Remove capacitor from unit Check for visual damage such as bulges cracks or leaks For dual rated apply an ohm...

Page 28: ...5 2 39 8239 25 10 52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58...

Page 29: ...Refrigerant The amount of the refrigerant is too much making the compressor load too big Recycle and recharge the refrigerant after checking for the reason Compressor The compressor is blocked inside...

Page 30: ...arefully rearrange tubing not to contact cabinet compressor shroud and barrier Water full alarm Water tank full Check and pour if the water tank is full Water depth sensor if failure Check and replace...

Page 31: ...the terminals Repair and correct if loose Temperature setting Check and adjust the temperature setting Mode setting Check and adjust the mode setting Compressor Check and replace if the compressor the...

Page 32: ...Exploded view spare part 30 12 Exploded view spare part 12 1 Exploded view of unit...

Page 33: ...Exploded view spare part 31 12 2 Exploded view of accessory part...

Page 34: ...0155 2 7 Pump 1 1 2240060019 2 8 Pump 2 1 2240060020 2 9 Pump fix plane 1 2122549022 2 10 Comp base pan 1 2122549017 2 11 Rubber 1 2272509015 2 12 Pump 1 drainage tube 1 2112549078 2 13 Pump 2 drainag...

Page 35: ...Assembly 1 2152539004 31 Fan motor Inner 1 2240042252 32 Compressor 1 2140062230 33 Cond Assembly 1 2152539006 34 Air outlet assembly 1 2112549118 34 1 Step motor 1 2240020039 35 Front plane assembly...

Reviews: