MCAC-UTSM-201707 Midea Tropical R410A High Efficient Duct Technical Manual 50Hz
80
clearance for air entrance to the condenser coil, for air discharge and for service access.
Notes: L1=1,000mm, L2=915mm.
For multiple unit installations, units must be spaced a minimum of 915mm apart. (Coil face to
face.
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit
should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of
hot air into the outdoor unit. At the same time, an adequated structural support for the unit is
necessary.
In case any obstacles exist above the outdoor unit, such obstacles must be 1,524mm above the
outdoor unit.
Ground installation:
The unit may be installed at ground level on a solid base that will not shift or settle, causing