Midea Tropical R410A High Efficient Duct Technical Manual 50Hz MCAC-UTSM-201707
37
MTA-36WN1 + MOVTB-36CN1-13C
Indoor
air flow
Outdoor
Temp. (DB)
IWB (°C)
15.0
17.2
19.4
21.7
IDB (°C)
21.1
23.9
26.7
29.4
21.1
23.9
26.7
29.4
21.1
23.9
26.7
29.4
21.1
23.9
26.7
29.4
1,000CFM
1,700m
3
/h
29.4
TC
32.8
32.8
33.5
34.2
34.9
34.9
34.9
35.6
37.1
37.1
37.1
37.1
/
39.3
39.3
39.3
SC
24.3
29.8
33.5
34.2
19.5
25.1
30.7
35.6
14.8
20.4
26.0
31.5
/
15.7
21.2
26.7
kW
2.58
2.58
2.58
2.58
2.58
2.58
2.58
2.58
2.59
2.59
2.59
2.59
/
2.60
2.60
2.60
35.0
TC
30.9
30.9
31.5
32.1
32.9
32.9
32.9
33.6
35.0
35.0
35.0
35.0
/
37.2
37.2
37.2
SC
23.5
28.7
31.5
32.1
18.8
24.3
29.6
33.6
14.0
19.6
25.2
30.5
/
14.9
20.5
26.0
kW
2.84
2.84
2.84
2.84
2.85
2.85
2.85
2.85
2.86
2.86
2.86
2.86
/
2.86
2.86
2.86
40.6
TC
28.9
29.5
30.1
30.7
30.8
30.8
30.8
31.4
32.8
32.8
32.8
32.8
/
34.9
34.9
34.9
SC
22.3
28.3
30.1
30.7
17.9
23.4
29.0
31.4
13.1
18.7
24.3
29.8
/
14.0
19.5
25.1
kW
3.13
3.13
3.13
3.13
3.14
3.14
3.14
3.14
3.16
3.16
3.16
3.16
/
3.18
3.18
3.18
46.1
TC
26.7
27.2
27.7
28.3
28.5
28.5
29.1
29.7
30.4
30.4
30.4
30.4
/
32.4
32.4
32.4
SC
21.4
27.2
27.7
28.3
16.8
22.2
27.9
29.7
12.2
17.6
23.1
28.6
/
13.0
18.5
24.0
kW
3.47
3.47
3.47
3.47
3.49
3.49
3.49
3.49
3.51
3.51
3.51
3.51
/
3.53
3.53
3.53
47.8
TC
26.4
26.9
27.4
27.9
28.2
28.2
28.8
29.4
30.1
30.1
30.1
30.7
/
32.1
32.1
32.1
SC
21.1
26.9
27.4
27.9
16.6
22.3
27.9
29.4
12.0
17.5
23.2
28.9
/
12.8
18.3
24.1
kW
3.59
3.59
3.59
3.59
3.60
3.60
3.60
3.60
3.62
3.62
3.62
3.62
/
3.65
3.65
3.65
51.7
TC
24.8
25.3
25.8
26.3
26.5
26.5
27.0
27.5
28.3
28.3
28.3
28.9
/
30.2
30.2
30.2
SC
20.3
25.3
25.8
26.3
15.9
21.5
27.0
27.5
11.3
16.7
22.4
28.0
/
12.1
17.8
23.3
kW
3.88
3.88
3.88
3.88
3.89
3.89
3.89
3.89
3.91
3.91
3.91
3.91
/
3.94
3.94
3.94
Notes:
1. IDB = Indoor Dry Bulb Temp. (°C); IWB = Indoor Wet Bulb Temp. (°C); TC = Total Cap. (1,000Btu/h); SC = Sensible Cap. (1,000Btu/h); kW = Power Input (kW).
Airflow Correction Factors
Air flow
TC
SC
kW
880CFM (1,496m
3
/h)
×0.98
×0.96
×0.99
1,130CFM (1,921m
3
/h)
×1.02
×1.06
×1.01