MCAC-2008-11 Air-cooled Modular Chiller
45
270 120
50
300 150
70
330 150
70
360 185
95
390 240 120
420 240 120
450
300 or 120×2
150
480
300 or 150×2
150
510
400 or 150×2
200
540
400 or 150×2
200
560
400 or 150×2
200
Remark:
The diameter selections of these preceding cables refer to allowable carrying capacity when
no-armored cables 0.6/1KV PVC with three or four-cores, insulation and PVC jacket lay the continuous
charge in air. Since different manufacturer with different models, qualities, laid situation and wiring distance
ect., the allowable carrying capacity of the cable will be got different influence. For example, if the wiring
length is very long, selecting the bigger model should be considered and the circuit voltage down should be
confirmed at the same time. So it is suggest that selecting cable should accord to the professional
electrician’s guidance and refer to the cable manufacturer’s technical manuals. The preceding list is only for
reference.
(3) The color requirement of wirings
Single-phased power wiring adopts the red wiring commonly, but the green, blue and yellow one also can be
used.
Three phase wirings (A, B, C) of the three-phased power wiring should use red, yellow and green in file.
5. Wiring connection of water flow switch
(1) The control wiring connection of water flow switch
The control wiring of water flow switch (prepared by customer) should be connected to main unit’s W1, W2
terminals on the PCB box. The following diagram and specification are for the water flow switch
WFS-1001-H produced by HONEYWELL and only be used for reference.
(2) Specification
Working pressure
10 bar
Touch point life
100 million periods
Compression resistance
10.5 bar
Ripple life
50 million periods
(3) Touch point capacity
Type
Voltage
Resistance charge
Lighting charge
Motor charge
AC inverter
125v~
5A
44A
5A
AC inverter
250v~
2.5A
22A
2.5A
DC inverter
115v-
0.3A
/
/
DC inverter
230v-
0.15A
/
/
(4) Water flow control range
Min. water flow (l/min)
Min. water flow (l/min)
Pipe diameter
(inch)
Flow flake
Closed value
Open value
Closed value
Open value
1
1
15 8 45 41
Summary of Contents for MGA-D30W/SN1
Page 23: ...MCAC 2008 11 Air cooled Modular Chiller 23 10 Exploded View 10 1 MGA F30W SN1...
Page 25: ...MCAC 2008 11 Air cooled Modular Chiller 25 10 2 MGA F65W SN1...
Page 27: ...MCAC 2008 11 Air cooled Modular Chiller 27 10 3 MGA D30W SN1...
Page 38: ...MCAC 2008 11 Air cooled Modular Chiller 38 Reference figure of water system installation...