MCAC-2008-11 Air-cooled Modular Chiller
18
8. Electric Characteristics
Outdoor Unit
Power Supply
Compressor
OFM
Model
Hz Voltage
Min. Max. MCA
TOCA
MFA
MSC
RLA
KW FLA
MGA-F30W/SN1 50 380 342 418 19.9
24
40
74×2
11.8×2
0.67 3.1
MGA-F65W/SN1 50 380 342 418 42.9
49
80
74×4
11.8×4
0.67×2
3.1×2
MGA-D30W/SN1 50 380 342 418 19.9
24
40 74/82.4 11.8/12.7 0.67 3.1
MGA-D65W/SN1 50 380 342 418 42.9
49
80 (74/82.4) ×2
(11.812.7) ×2
0.67×2
3.1×2
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Locked Rotor Amps. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Input (kW)