MCAC-2008-11 Air-cooled Modular Chiller
19
9. Capacity Tables
9.1 Cooling:
MGA-F30W/SN1 MGA-D30W/SN1
Condensed water outlet temp. ( )
℃
5 7 9 12
Ambient temp.
Difference of water
inlet and outlet temp.
Capacity
Water flow
Power
Capacity
Water flow
Power
Capacity
Water flow
Power
Capacity
Water flow
Power
( )
℃
( )
℃
kW
m
3
/h kW kW m
3
/h kW kW m
3
/h kW kW m
3
/h kW
3
8.9 9.5 9.9 10.2
4
6.7 7.1 7.4 7.6
25
5
31.2
5.4
8.6 33.1
5.7
8.8 34.4
5.9
9.0 35.5
6.1
9.3
3
8.9 9.3 9.7 10.1
4
6.6 7.0 7.3 7.5
28
5
30.9
5.3
8.8 32.4
5.6
8.9 33.9
5.8
9.1 35.1
6.0
9.4
3
8.6 9.0 9.5 9.9
4
6.4 6.8 7.1 7.4
30
5
29.9
5.1
9.2 31.5
5.4
9.3 33.0
5.7
9.5 34.7
6.0
9.8
3
8.4 8.9 9.4 9.8
4
6.3 6.7 7.0 7.4
32
5
29.2
5.0
9.4 31.2
5.4
9.5 32.7
5.6
9.7 34.2
5.9
10.0
3
8.2 8.6 9.1 9.5
4
6.1 6.4 6.8 7.1
35
5
28.5
4.9
9.7 30.0
5.2
10.0 31.8
5.5
10.3 33.0
5.7
10.5
3
7.9 8.3 8.8 9.1
4
5.9 6.3 6.6 6.8
38
5
27.6
4.7
10.3 29.1
5.0
10.5 30.6
5.3
10.8 31.8
5.5
10.8
3
7.7 8.1 8.5 8.9
4
5.8 6.1 6.4 6.7
40
5
27.0
4.6
10.6 28.2
4.8
10.8 29.7
5.1
11.1 31.2
5.4
11.1
Summary of Contents for MGA-D30W/SN1
Page 23: ...MCAC 2008 11 Air cooled Modular Chiller 23 10 Exploded View 10 1 MGA F30W SN1...
Page 25: ...MCAC 2008 11 Air cooled Modular Chiller 25 10 2 MGA F65W SN1...
Page 27: ...MCAC 2008 11 Air cooled Modular Chiller 27 10 3 MGA D30W SN1...
Page 38: ...MCAC 2008 11 Air cooled Modular Chiller 38 Reference figure of water system installation...