background image

MCAC-ATSM-2014-01 

R410A Mini Split Chiller 50Hz 

 

29 

15. Sound Levels 

          MGA-D10/N1                                                    MGA-D12/N1, MGA-D14/SN1, MGA-D16/SN1 

Microphone

Outdoor Unit

H

1.0m

       

 

          Note: 

H= 0.5 × height of outdoor unit                 

Note: 

The point A is in the middle of the whole outdoor 

 

panel. 

 

Model 

Noise level dB(A) 

MGA-D10/N1 

57 

MGA-D12/N1 

60 

MGA-D14/SN1 

60 

MGA-D16/SN1 

60 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for MGA-D10/N1

Page 1: ...ions 12 8 Service Space 13 9 Piping Diagram 14 10 Wiring Diagrams 15 11 Electric Characteristics 17 12 Capacity Tables 18 13 Operation Limits 26 14 Hydraulic Performance 28 15 Sound Levels 29 16 Explo...

Page 2: ...pe Digital scroll Heat pump CE SBX N1 01 220 240 1 50 MGA D12 N1 R410A 12 Plate type Digital scroll Heat pump CE SBX N1 01A 220 240 1 50 MGA D14 SN1 R410A 14 Plate type Digital scroll Heat pump CE SBX...

Page 3: ...M G A D 14 S N1 Refrigerant N1 R410A Power supply S 380 415V 50Hz 3Ph 220 240V 50Hz 1Ph Capacity 14kW Compressor type D Digital scroll compressor F Fixed scroll compressor Product series code A Split...

Page 4: ...system no need cooling water tower packaged design easy for installation 4 3 Energy saving and high reliability a By adopting Copeland digital scroll compressor the capacity can be stepless adjusted...

Page 5: ...ater pump Water flow switch 4 5 Wired controller KJRM 120D BMK E Standard The setting and operation order can be send to the main board and the running condition can be displayed by the wired controll...

Page 6: ...n motor is six pole electric motor with built in thermal cut out Evaporator in the water pump box The heat exchanger is made of AISI 316 stainless steel to ensure high heat exchange efficiency complet...

Page 7: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 7 Outdoor unit MGA D10 N1 MGA D12 N1 MGA D14 SN1 MGA D16 SN1 Water pump box...

Page 8: ...elling Input Hi Lo W 326 200 185 120 2 Capacitor uF 10uF 5 450V 5uF 450V Speed Hi Lo r min 740 530 860 610 Outdoor condenser coil Number of rows 2 2 Tube pitch a x row pitch b mm 25 4 22 25 4 22 Fin s...

Page 9: ...Liquid side mm 9 53 9 53 Gas side mm 19 19 Pipe diameter Water inlet outlet mm DN32 DN32 Controller Wired controller KJRM 120D BMK E Ambient temperature Cooling 10 43 Cooling 10 43 Heating 15 24 Heat...

Page 10: ...Number of rows 2 3 Tube pitch a x row pitch b mm 25 4 22 25 4 22 Fin spacing mm 1 5 1 5 Fin type Hydrophilic aluminum Hydrophilic aluminum Tube outside diameter and type mm 9 53 9 53 Inner grooved tu...

Page 11: ...controller KJRM 120D BMK E Ambient temperature Cooling 10 43 Cooling 10 43 Heating 15 24 Heating 15 24 Note The specification is based on the following conditions 1 Cooling mode ambient temperature 35...

Page 12: ...AC ATSM 2014 01 12 7 Dimensions 7 1 Outdoor unit Unit mm Dimensions Model A B C D E MGA D10 N1 990 966 340 624 366 MGA D12 N1 940 1250 340 600 376 MGA D14 SN1 940 1250 340 600 376 MGA D16 SN1 940 1250...

Page 13: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 13 8 Service Space...

Page 14: ...agram Remark No Name No Name No Name 1 Compressor 6 Capillary 11 Liquid receiver 2 High pressure switch 7 Liquid receiver 12 Low pressure switch 3 4 way valve 8 Plate heat exchanger 13 Crankcase heate...

Page 15: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 15 10 Wiring Diagrams 10 1 MGA D10 N1...

Page 16: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 16 10 2 MGA D12 N1 10 3 MGA D14 SN1 MGA D16 SN1...

Page 17: ...8 7 54 34 8 10A MGA D12 N1 220 240 1 50 5 0 23 2 147 0 37 1 6 0 5 2 2 5 8 27 7 63 35 1 10A MGA D14 SN1 380 415 3 50 5 75 9 8 82 4 0 37 1 6 0 5 2 2 6 62 13 6 8 6 17 7 10A MGA D16 SN1 380 415 3 50 5 75...

Page 18: ...7 11 0 11 3 Pa kW 3 3 3 3 3 4 3 4 3 5 3 5 Pat kW 3 8 3 8 3 9 3 9 4 0 4 0 Qev m3 h 1 7 1 7 1 8 1 9 1 9 2 0 Pev kPa 40 5 41 3 45 0 48 0 48 6 51 0 40 Pf kW 9 4 9 7 10 0 10 3 10 6 11 0 Pa kW 3 6 3 6 3 7...

Page 19: ...4 2 4 2 4 3 4 3 4 3 Pat kW 4 8 4 8 4 8 4 9 4 9 4 9 Qev m3 h 2 0 2 0 2 1 2 1 2 2 2 2 Pev kPa 33 8 37 1 40 6 43 2 46 1 48 0 40 Pf kW 10 9 11 2 11 5 11 8 12 1 12 4 Pa kW 4 5 4 5 4 5 4 6 4 6 4 6 Pat kW 5...

Page 20: ...4 6 4 6 4 7 4 7 4 7 Pat kW 5 1 5 1 5 1 5 2 5 2 5 2 Qev m 3 h 2 3 2 4 2 4 2 5 2 5 2 5 Pev kPa 40 8 43 5 44 2 46 9 47 8 48 3 40 Pf kW 12 5 12 8 13 1 13 4 13 7 14 0 Pa kW 5 1 5 1 5 1 5 2 5 2 5 2 Pat kW 5...

Page 21: ...4 9 4 9 5 0 5 0 5 0 Pat kW 5 7 5 7 5 7 5 8 5 8 5 8 Qev m3 h 2 6 2 6 2 7 2 7 2 8 2 8 Pev kPa 50 8 53 1 55 8 58 1 61 2 63 2 40 Pf kW 13 9 14 2 14 5 14 8 15 1 15 2 Pa kW 5 3 5 3 5 3 5 4 5 4 5 4 Pat kW 6...

Page 22: ...4 7 Pat kW 4 6 4 9 5 2 5 5 Qc m 3 h 2 2 2 2 2 2 2 2 Pc kPa 37 2 35 8 34 5 33 1 10 Pt kW 12 3 12 2 12 1 12 0 Pa kW 3 9 4 2 4 5 4 8 Pat kW 4 7 5 0 5 3 5 1 Qc m 3 h 2 3 2 3 2 3 2 3 Pc kPa 40 5 40 0 39 2...

Page 23: ...kW 4 7 5 0 5 3 5 6 Qc m 3 h 2 4 2 4 2 4 2 4 Pc kPa 44 0 43 6 43 1 42 8 10 Pt kW 15 2 15 1 15 0 14 9 Pa kW 4 0 4 3 4 6 4 9 Pat kW 4 8 5 1 5 4 5 7 Qc m 3 h 2 5 2 5 2 5 2 5 Pc kPa 38 0 37 6 37 2 37 0 15...

Page 24: ...kW 4 9 5 3 5 8 6 3 Qc m 3 h 2 8 2 8 2 8 2 8 Pc kPa 31 2 31 1 31 0 31 0 10 Pt kW 17 6 17 5 17 4 17 4 Pa kW 4 2 4 6 5 1 5 6 Pat kW 5 0 5 4 5 9 6 4 Qc m 3 h 3 1 3 1 3 1 3 1 Pc kPa 36 4 36 2 36 0 35 9 15...

Page 25: ...kW 5 1 5 5 6 0 6 5 Qc m 3 h 2 9 2 9 2 9 2 9 Pc kPa 30 2 30 1 30 0 30 0 10 Pt kW 18 7 18 6 18 5 18 4 Pa kW 4 4 4 8 5 3 5 8 Pat kW 5 2 5 6 6 1 6 6 Qc m 3 h 3 2 3 2 3 2 3 2 Pc kPa 35 4 35 2 35 0 34 8 15...

Page 26: ...0 96 0 955 cQ 1 1 02 1 04 1 075 1 11 1 14 cdp 1 1 07 1 11 1 18 1 22 1 24 cPf correction factor refrigerating capacity cQ correction factor flow rate cdp correction factor pressure drop Note 1 During w...

Page 27: ...ower input correction factor 13 3 Minimum water volume Model MGA D10 N1 MGA D12 N1 MGA D14 SN1 MGA D16 SN1 Minimum water volume L 43 50 60 68 If the total water volume in the system is less than the v...

Page 28: ...nger pressure drop water side Model Water flow m 3 h 0 8 1 0 1 2 1 4 1 6 1 8 2 0 l sec 0 222 0 278 0 333 0 389 0 444 0 500 0 556 MGA D10 N1 Pressure drop kPa 26 29 33 37 42 46 50 Model Water flow m 3...

Page 29: ...Levels MGA D10 N1 MGA D12 N1 MGA D14 SN1 MGA D16 SN1 Microphone Outdoor Unit H 1 0m Note H 0 5 height of outdoor unit Note The point A is in the middle of the whole outdoor panel Model Noise level dB...

Page 30: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 30 16 Exploded Views 16 1 MGA D10 N1 Matched water pump box CE SBX N1 01...

Page 31: ...ss y 1 7 22 Power supply wire 1 28 Discharge temp sensor ass y 1 7 23 Main control board ass y 1 29 Discharge temp sensor 1 7 24 Outdoor communication cable 1 Water pump box CE SBX N1 01 No Part Name...

Page 32: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 32 16 2 MGA D12 N1 Matched water pump box CE SBX N1 01A...

Page 33: ...xing ring 1 10 1 Low pressure valve 1 31 Rear support board II 1 Water pump box CE SBX N1 01A No Part Name Quantity No Part Name Quantity 1 Up covering plate 1 18 2 Branch pipe 2 2 Water inlet pipe as...

Page 34: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 34 16 3 MGA D14 SN1 Matched water pump box CE SBX SN1 01...

Page 35: ...way valve ass y 1 31 Rear support board II 1 Water pump box CE SBX SN1 01 No Part Name Quantity No Part Name Quantity 1 Up covering plate 1 18 2 Branch pipe 2 2 Water inlet pipe ass y 1 18 3 Screw 1 2...

Page 36: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 36 16 4 MGA D16 SN1 Matched water pump box CE SBX SN1 01A...

Page 37: ...lve ass y 1 31 Rear support board II 1 Water pump box CE SBX SN1 01A No Part Name Quantity No Part Name Quantity 1 Up covering plate 1 18 2 Branch pipe 2 2 Water inlet pipe ass y 1 18 3 Screw 1 2 1 Pi...

Page 38: ...e Malfunction E0 Water flow test malfunction P0 Current protection E1 Power phase sequence malfunction P1 High pressure protection E2 Indoor outdoor unit communication checking channel is abnormal P2...

Page 39: ...utlet water 10 Water flow switch gets faulty Yes Check the water system and clean the filter Yes Check the water pump and repair or replace it if necessary No Yes Check the water flow switch and repai...

Page 40: ...er supply lacks phase Check whether the phase order of 3 phase power supply is incorrect Yes Check the power supply and power wire Yes Exchange the power wire of any two phases No LED indicates E2 Che...

Page 41: ...he inlet water temperature sensor is broken see whether the resistance of inlet water temperature sensor is wrong No Yes Replace the inlet water temperature sensor LED indicates E4 Check whether the w...

Page 42: ...hether the outlet water temperature sensor is broken see whether the resistance of outlet water temperature sensor is wrong No Yes Replace the outlet water temperature sensor LED indicates E6 Check wh...

Page 43: ...exchanger temperature sensor 1 is broken see whether the resistance of plate heat exchanger temperature sensor is wrong No Yes Replace the plate heat exchanger temperature sensor 1 LED indicates E8 Ch...

Page 44: ...is blocked by sundries Yes Clear the sundries to ensure smooth discharge Check whether the condenser coil fin gets dirty No Yes Clean the condenser No Check whether the ambient temperature is too high...

Page 45: ...the refrigerant No Check whether the power voltage is too low For 1 phase unit power voltage 198V for 3 phase unit 342V Yes Check and repair the power supply No Check whether air outlet is blocked by...

Page 46: ...ether the outdoor ambient temperature is too high Yes Stop the unit No Check whether the outdoor unit is bad ventilation Yes Make the outdoor unit ventilate well No Check whether the heat exchanger is...

Page 47: ...s too low No The refrigerant of the system leakage Yes Validate Connect the pressure gauge to the gauge joint of the system check whether the pressure is lower than 0 15MPa The refrigerant pipe is blo...

Page 48: ...heck whether the sequence of the four temperature sensor kits in the water pump is wrong connected No Yes Fix it well Check whether outdoor ambient temperature is too high Compressor motor gets faulty...

Page 49: ...ature sensor kit at the plate heat exchanger side gets faulty Yes Replace the temperature sensor kit The heat exchange of water side is insufficient No Yes Clean the water side heat exchanger or pipe...

Page 50: ...troller displays P4 Refer to the P4 to solve the problem LED indicates Pb Check whether the circulation water is insufficient Q 0 6 Qrated Yes Check the water system and make adjustment Check whether...

Page 51: ...or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Do not touch...

Page 52: ...long enough to allow positioning of the lifting slings and safety pins in the feet on the unit To avoid the slings damaging the unit place protection between the slings and the unit Position the unit...

Page 53: ...sure there is no any dirt or water in the piping before connecting it to the outdoor unit Please clean the piping with high pressure nitrogen rather than refrigerant of outdoor unit e Vacuuming with...

Page 54: ...oosen the joint nut of stop valve A a little 3 For 3 5m s piping turn the valve rod of B anticlockwise to 45 for about 6 7seconds After the air is expelled from A fasten the joint nut of stop valve A...

Page 55: ...e is much salty ingredients There is caustic gas such sulfide in the air The copper tubes and welding parts will be rusted and damaged causing refrigerant to leak There is mineral oil cooking oil or g...

Page 56: ...oid it weighing on the unit It is recommended that the following devices are installed in the water circuit of the evaporator A hydraulic safety valve shall be mounted in water system which should ope...

Page 57: ...drain cock outside the unit and all the installation and terminal air vent valves Size and position of connections Model MGA D10 N1 MGA D12 N1 MGA D14 SN1 MGA D16 SN1 Water inlet outlet R5 4 R5 4 R5...

Page 58: ...against short circuits and leakage to earth isolating the installation from other equipment phase units the unbalance between the phases must not exceed 3 If these parameters are not respected contac...

Page 59: ...VV 450 750 5 4 0 mm 2 For outdoor unit 10 5 12 14 16kW Water flow controlling wire 1 AWG24 7 core shielding wire Between outdoor unit and water pump box Temp Sensor signal wire shielding wire 1 RVV 30...

Page 60: ...tance Service maintenance plan must be observed with an annual service which includes the following operations and checks Filling of the water circuit Presence of air bubbles in the water circuit Effi...

Page 61: ...it must be completely emptied before being refilled The R410A refrigerant must only be filled in the liquid state Operating conditions other than nominal conditions may produce considerably different...

Page 62: ...ay when the electric auxiliary heating water function is operated 4 Check Display when check function is operated 5 Anti freezing Display when the main unit ambient temperature is below 2 to remind th...

Page 63: ...g press this key for 3 seconds and enter to spot checking 14 Add Reduce key Setting water temperature timing water level etc during spot check they are used to read over 0 15 units 15 Cancel key Durin...

Page 64: ...s the hour of Timer 1 On press the or to adjust press key when finished and then the minute of the clock will flash it means the current setting is the minute of Timer 1 On press the or to adjust pres...

Page 65: ...mer 1 to be 07 10 and O ff time of Timer 1 Off to be 12 30 then back to the main page Finish setting the On time of Timer 1 to be 07 10 and Off time to be 12 30 then enter the setting of Timer 2 Wheth...

Page 66: ...ur of the clock will flash it means the current setting is the hour of the clock press the or to adjust press key when finished and then the minute of the clock will flash it means the current setting...

Page 67: ...tton The address range 0 15 therefore 16 wired controller could be parallel at most Operation method Press Constraint two button for 3 seconds to enter the wired remote address selection Press or key...

Page 68: ...hat means the corresponding outdoor unit has error or protection at that time and then can spot check the last 1 2 3 times error or protection of this outdoor unit After clear the error or protection...

Page 69: ...ure of wired controller 10 C 43 C 3 Operating RH of wired controller RH 40 RH90 20 1 8 Main functions of this wired controller as follows 1 Touch key operation 2 LCD displays operation parameters 3 Mu...

Page 70: ...mation such as temperature value timing In the startup status press this button once and the startup indicator led goes off and transmits the shutdown information Operation mode button In the power of...

Page 71: ...ays the last fault information and the protection information when query is conducted on fault and protection information 2 outdoor pipe temperature T3A protection Error outlet water temperature Tou c...

Page 72: ...vious modular will display if the current modular is 0 and the previous one is 15 Press this button for minus address at wire address setting mode If the wired controller address is 0 press this key w...

Page 73: ...dure of water temperature setting 1 Press TEMP SET button of wired controller when background light is on 2 Press ADDRESS or ADDRESS button you can select the water temperature Temperature range is no...

Page 74: ...t alarm handing 1 When unit fails or the wire controller detects failure of communication with the the outdoor units the indicator blinks After all fault of the system and the wire controller are elim...

Page 75: ...he timing startup function 5 Real time clock function the wired controller inner place 3V battery When the wired controller is powered on the LCD will display the current time if it is powered off the...

Page 76: ...nly one unit is connected The wiring procedure and principles are shown in the figure P Black Q Gray E Yellow Y X Outdoor electric control box Communicate with upper unit reserved Please use 3 cord wi...

Page 77: ...SET Set Period 1 end hour ADDRESS ADDRESS or Set Period 1 end minute ADDRESS ADDRESS or Set Period 1 mode ADDRESS ADDRESS or Set Period 1 temperature ADDRESS ADDRESS Set Timer Period 2 or ADDRESS Set...

Page 78: ...ording to memorized status before power failure in order to ensure that the unit can run in the originally set status after restoration of the power supply 2 In the normal status the background light...

Page 79: ...nstall it correctly or will damage the control panel or battery even worse will put lives at risk Note The gateway will be used with wired controller together The LONWORKS gateway can be use independe...

Page 80: ...41164 4 44 36 6 13059 76 1 34105 116 0 4006 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1 37 1988 39 5 39689 79 1 2133 119 0 36954 0 35 2024 40 5 17519 80...