Midea R410A T3 50Hz Top-discharge Series MCAC-UTSM-201707
85
Symptom
Possible causes
Way of handing
The cooling effect is
poor.
The condenser or evaporator is
too dirty.
Clean the heat-exchanger.
The filter is blocked.
Clean the filter.
The intake orifice or exhaust
orifice of the indoor and outdoor
unit is blocked.
Remove foreign matters to keep well
ventilated.
The door or window is opened.
Close all the windows and doors.
Directly exposed to sunlight.
Obstruct sunlight by curtains or
jalousie.
Too many heat sources.
Reduce heat sources.
Too high outdoor environment
temperature.
It is normal, and the cooling effect of the
air conditioner is deteriorated.
The refrigerant is leaked or the
replenishment is deficient.
Detect leak, and fill the refrigerant of a
correct quantity.
Symptom
Possible causes
Way of handing
The unit keep
starting up and
shutting down
frequently
The refrigerant is excessive or
deficient.
Detect leak, and fill the refrigerant of a
correct quantity.
Air or non-condensable gas
exists in the refrigerant loop.
Make a vacuum again and fill the
refrigerant.
The compressor fails.
Repair or replace the compressor.
The voltage is too high or too
low.
Install a voltage regulator.
The refrigerant loop is
obstructed.
Locate the causes and replace the part.
11.3 Faults of remote controller and cause
Before requesting for maintenance or repair, inspect the following:
The shift function cannot be set.
Symptom
Check item
Cause
The wind speed
cannot be shifted.
Check whether the mode
marked the screen of controller
is
AUTO
.
When you select the
AUTO
mode, the
indoor unit will select “
AUTO
” for the air
speed automatically
Check whether the mode
marked on the controller screen
is
DEWET
.
When the dry mode is selected, the
indoor unit will set fan speed
automatically. The speed can
selectable only in cooling, heating and
fan mode.
Summary of Contents for MFA3T-96CRN1
Page 15: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 14 3 Service Space...
Page 18: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 17 MTB1T 96HWN1 MHB1T 96HWN1...
Page 31: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 30 4 Service Space...
Page 33: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 32 6 Wiring Diagrams MFA3T 96CRN1...
Page 34: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 33 MFA3T 96HRN1...
Page 46: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 45 4 Wiring Diagrams MOVTA 96CN1 R...