There is natural drain, it is should be confirmed that the height of drain pipe is not higher
than water collection tray.
The number of bends and folds of the drain pipe should not exceed 2. Try to avoid bends to
prevent trash accumulation.
Open the side panel of the indoor unit, fill water inward, and check whether water can be
drained smoothly. Check whether water leak at the joint.
After making sure that water drains smoothly and no water is leaked, use adiabatic wool
bushes to preserve heat of the drain pipe. Ohterwise, condensate will occur.