MCAC-VTSM-2016-10
R410A All DC Inverter Mini VRF
Specifications&Performance 13
Notes:
1. The cooling conditions: indoor temp.: 27
℃
DB (80.6
℉
), 19
℃
WB (66.2
℉
) outdoor temp.: 35
℃
DB (95
℉
), 24
℃
WB (75.2
℉
)
equivalent pipe length: 5m drop length: 0m.
2. The heating conditions: indoor temp.: 20
℃
DB (68
℉
), 15
℃
WB (59
℉
) outdoor temp.: 7
℃
DB (44.6
℉
), 6
℃
WB (42.8
℉
)
equivalent pipe length: 5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(1.2m for
120~180 model). During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. The aboved datas may be changed without notice for future improvement on quality and performance.
Coil length x
height
mm
1276 x 870
1276 x 870
Number of
circuits
7
12
Outdoor air flow
m
3
/h
6000
6800
Outndoor sound level(sound
pressure level )
dB(A)
57
59
Outdoor unit
Dimension
(W x H x D)
mm
900 x 1327 x 400
900 x 1327 x 400
Packing
(W x H x D)
mm
1030 x 1456 x 435
1030 x 1456 x 435
Net/Gross weight
kg
102/113
107/118
Refrigerant
Type
R410A
R410A
Charged volume
g
3900
4500
Throttle type
Electronic expansion valve
Design pressure
MPa
4.4/2.6
4.4/2.6
Refrigerant
piping
Liquid side/ Gas
side
mm
Ф9.53/Ф19.1
Ф9.53/Ф19.1
Max.
refrigerant
pipe length
m
100
100
Max. difference in
level
m
8
8
Connection
wiring
Power wiring
mm
2
5 core x2.5
5 core x2.5
Signal wiring
mm
2
3 core shielded wire x 0.75
3 core shielded wire x 0.75
Ambient temp
℃
(
Cooling -15
~
43
)
(
Heating -15
~
27
)
(
Cooling -15
~
43
)
(
Heating -15
~
27
)