MCAC-VTSM-2016-02
R410a All DC Inverter Mini VRF
Specifications&Performance 29
MDV-140W/DGN1
Cooling
Combination
(%)
(Capacity
index)
Outdoor
temperature
(°C DB)
Indoor temperature(
°C
DB/WB)
DB:20.8,WB:14
DB:23.3,WB:16
DB:25.8,WB:18
DB:27,WB:19
DB:28.2,WB:20
DB:30.7,WB:22
DB:32,WB:24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-5
4.7
0.64
5.6
0.74
6.5
0.85
7.0
0.89
7.5
0.94
8.4
1.06
9.3
1.15
-2
4.7
0.64
5.6
0.75
6.5
0.86
7.0
0.90
7.5
0.95
8.4
1.08
9.3
1.16
0
4.7
0.65
5.6
0.77
6.5
0.87
7.0
0.91
7.5
0.96
8.4
1.10
9.3
1.18
2
4.7
0.66
5.6
0.77
6.5
0.89
7.0
0.93
7.5
0.98
8.4
1.10
9.3
1.21
4
4.7
0.67
5.6
0.79
6.5
0.90
7.0
0.94
7.5
1.00
8.4
1.13
9.3
1.24
6
4.7
0.68
5.6
0.80
6.5
0.91
7.0
0.96
7.5
1.02
8.4
1.15
9.3
1.27
8
4.7
0.70
5.6
0.81
6.5
0.93
7.0
0.98
7.5
1.03
8.4
1.16
9.3
1.31
10
4.7
0.71
5.6
0.82
6.5
0.94
7.0
0.99
7.5
1.06
8.4
1.20
9.3
1.33
12
4.7
0.72
5.6
0.83
6.5
0.96
7.0
1.01
7.5
1.08
8.4
1.22
9.3
1.35
14
4.7
0.73
5.6
0.84
6.5
0.97
7.0
1.04
7.5
1.10
8.4
1.24
9.3
1.38
16
4.7
0.74
5.6
0.86
6.5
0.98
7.0
1.05
7.5
1.12
8.4
1.26
9.3
1.40
18
4.7
0.75
5.6
0.87
6.5
1.00
7.0
1.07
7.5
1.14
8.4
1.28
9.3
1.43
20
4.7
0.76
5.6
0.88
6.5
1.01
7.0
1.08
7.5
1.16
8.4
1.30
9.3
1.46
21
4.7
0.77
5.6
0.89
6.5
1.03
7.0
1.09
7.5
1.17
8.4
1.32
9.3
1.47
23
4.7
0.78
5.6
0.90
6.5
1.04
7.0
1.12
7.5
1.19
8.4
1.34
9.3
1.50
25
4.7
0.79
5.6
0.92
6.5
1.06
7.0
1.14
7.5
1.23
8.4
1.41
9.3
1.60
27
4.7
0.80
5.6
0.96
6.5
1.12
7.0
1.21
7.5
1.30
8.4
1.50
9.3
1.71
29
4.7
0.84
5.6
1.01
6.5
1.19
7.0
1.29
7.5
1.39
8.4
1.59
9.3
1.82
31
4.7
0.89
5.6
1.07
6.5
1.26
7.0
1.37
7.5
1.47
8.4
1.69
9.3
1.94
33
4.7
0.95
5.6
1.13
6.5
1.34
7.0
1.44
7.5
1.56
8.4
1.80
9.3
2.06
35
4.7
1.00
5.6
1.20
6.5
1.41
7.0
1.53
7.5
1.65
8.4
1.91
9.3
2.19
37
4.7
1.05
5.6
1.26
6.5
1.50
7.0
1.62
7.5
1.75
8.4
2.03
9.3
2.33
39
4.7
1.11
5.6
1.33
6.5
1.58
7.0
1.72
7.5
1.86
8.4
2.15
9.3
2.47
41
4.7
1.16
5.6
1.39
6.5
1.64
7.0
1.80
7.5
1.94
8.4
2.27
9.3
2.59
43
4.7
1.23
5.6
1.49
6.5
1.70
7.0
1.88
7.5
1.99
8.4
2.38
9.3
2.70
45
4.7
1.26
5.6
1.52
6.5
1.81
7.0
2.02
7.5
2.07
8.4
2.61
9.3
2.93
Note:
1
.
is tested under our standard condition.
2
.
The above table shows the average value of conditions may operate.
3
.
It is recommended to connect less than 130%.