MCAC-VTSM-2016-02
R410a All DC Inverter Mini VRF
Specifications&Performance 37
MDV-160W/DGN1
Cooling
Combination
(%)
(Capacity
index)
Outdoor
temperature
(°C DB)
Indoor temperature(
°
C DB/WB)
DB:20.8,WB:14
DB:23.3,WB:16
DB:25.8,WB:18
DB:27,WB:19
DB:28.2,WB:20
DB:30.7,WB:22
DB:32,WB:24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-5
5.4
0.75
6.5
0.87
7.5
1.00
8.0
1.05
8.5
1.11
9.5
1.26
10.6
1.36
-2
5.4
0.76
6.5
0.89
7.5
1.01
8.0
1.06
8.5
1.13
9.5
1.28
10.6
1.38
0
5.4
0.77
6.5
0.91
7.5
1.03
8.0
1.08
8.5
1.14
9.5
1.30
10.6
1.40
2
5.4
0.78
6.5
0.92
7.5
1.05
8.0
1.10
8.5
1.16
9.5
1.30
10.6
1.43
4
5.4
0.79
6.5
0.93
7.5
1.06
8.0
1.11
8.5
1.18
9.5
1.34
10.6
1.46
6
5.4
0.81
6.5
0.95
7.5
1.08
8.0
1.13
8.5
1.21
9.5
1.36
10.6
1.51
8
5.4
0.83
6.5
0.96
7.5
1.10
8.0
1.16
8.5
1.22
9.5
1.38
10.6
1.55
10
5.4
0.84
6.5
0.97
7.5
1.11
8.0
1.18
8.5
1.26
9.5
1.41
10.6
1.58
12
5.4
0.85
6.5
0.99
7.5
1.13
8.0
1.20
8.5
1.28
9.5
1.44
10.6
1.60
14
5.4
0.86
6.5
1.00
7.5
1.14
8.0
1.23
8.5
1.30
9.5
1.46
10.6
1.63
16
5.4
0.87
6.5
1.01
7.5
1.16
8.0
1.24
8.5
1.32
9.5
1.49
10.6
1.66
18
5.4
0.89
6.5
1.03
7.5
1.18
8.0
1.26
8.5
1.35
9.5
1.51
10.6
1.69
20
5.4
0.90
6.5
1.04
7.5
1.20
8.0
1.28
8.5
1.37
9.5
1.54
10.6
1.72
21
5.4
0.91
6.5
1.06
7.5
1.21
8.0
1.29
8.5
1.38
9.5
1.56
10.6
1.74
23
5.4
0.92
6.5
1.07
7.5
1.23
8.0
1.32
8.5
1.41
9.5
1.58
10.6
1.78
25
5.4
0.93
6.5
1.09
7.5
1.26
8.0
1.35
8.5
1.45
9.5
1.67
10.6
1.90
27
5.4
0.95
6.5
1.13
7.5
1.33
8.0
1.43
8.5
1.54
9.5
1.77
10.6
2.02
29
5.4
1.00
6.5
1.19
7.5
1.41
8.0
1.52
8.5
1.64
9.5
1.89
10.6
2.16
31
5.4
1.06
6.5
1.26
7.5
1.49
8.0
1.62
8.5
1.74
9.5
2.00
10.6
2.29
33
5.4
1.12
6.5
1.34
7.5
1.58
8.0
1.71
8.5
1.85
9.5
2.13
10.6
2.44
35
5.4
1.18
6.5
1.41
7.5
1.67
8.0
1.81
8.5
1.95
9.5
2.26
10.6
2.59
37
5.4
1.24
6.5
1.50
7.5
1.77
8.0
1.92
8.5
2.07
9.5
2.40
10.6
2.75
39
5.4
1.31
6.5
1.58
7.5
1.87
8.0
2.03
8.5
2.20
9.5
2.55
10.6
2.92
41
5.4
1.37
6.5
1.65
7.5
1.94
8.0
2.12
8.5
2.29
9.5
2.68
10.6
3.06
43
5.4
1.46
6.5
1.76
7.5
2.01
8.0
2.22
8.5
2.35
9.5
2.82
10.6
3.19
45
5.4
1.49
6.5
1.80
7.5
2.14
8.0
2.39
8.5
2.45
9.5
3.09
10.6
3.47
Note:
1
.
is tested under our standard condition.
2
.
The above table shows the average value of conditions may operate.
3
.
It is recommended to connect less than 130%.