![Midea MCHS-09PSH1 Service Manual Download Page 41](http://html1.mh-extra.com/html/midea/mchs-09psh1/mchs-09psh1_service-manual_1790756041.webp)
9.3.6 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code
EC
Malfunction decision
conditions
Define the evaporator coil temp.T2 of the compressor just starts
running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2
<
Tcool
-
2
°C(Tcool
-
35.6
°F) does not keep continuous 4
seconds and this situation happens 3 times, the display area will
show “EC” and AC will turn off.
Supposed causes
●
T2 sensor faulty
●
Indoor PCB faulty
●
System problems, such as leakage or blocking.
Trouble shooting:
Summary of Contents for MCHS-09PSH1
Page 1: ...Mission 3D Inverter Series Service Manual 2016 MBSUL A 1604...
Page 8: ...For 9k 12k For 18k 24k For 30k 36k...
Page 11: ...5 Wiring Diagram 5 1 Indoor Unit MEHS 09PSH1 MEHS 12PSH1 MEHSU 09PHH2 MEHSU 12PHH2...
Page 12: ...MEHSU 18PHH2 MEHSU 24PHH2 MEHS 30PSH2 MEHS 36PSH2...
Page 13: ...5 2 Outdoor Unit MCHS 09PSH1 MCHS 12PSH1 MCHSU 09PHH2 MCHSU 12PHH2 MCHSU 18PHH2...
Page 14: ...MCHSU 24PHH2 MCHS 30PSH2 MCHS 36PSH2...
Page 45: ...P W N U...
Page 46: ...N V N W...
Page 78: ...compressor on bottom plate 4 Lift the compressor from the base pan assembly 3...