12
1)
Connect the charge hose to the charging
cylinder and open the 2-way and 3-way
valves.
With the charge hose you disconnected
from the vacuum pump, connect it to the
valve at the bottom of the cylinder.
If the refrigerant is R410A, place the
cylinder bottom-up to ensure liquid charging
is possible.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder
and press the check valve on the charge set
(be careful of the liquid refrigerant).
3) Place the charging cylinder onto the
electronic scale and record the weight.
4) Turn on the air conditioner in cooling
mode.
5) Open the valves (Low side) on the charge
set. Charge the system with liquid refrigerant.
6).When the electronic scale displays the
proper weight (refer to the table), disconnect
the charge hose from the 3-way valve’s
service port immediately and turn off the air
conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service
port
Use a torque wrench to tighten the service
port cap to a torque of 18N.m(13.27 ft·lbs).
Be sure to check for gas leaks.
4.5 Adding Refrigerant after Long-
Term System Operation
Procedure
1)
Connect the charge hose to the 3-way
service port and open the 2-way and 3-way
valve.
Connect the charge hose to the valve at the
bottom of the cylinder. If the refrigerant is
R410A, place the cylinder bottom-up to
ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder
and press the check valve on the charge set
to purge the air (be careful of the liquid
refrigerant).
3) Place the charging cylinder onto the
electronic scale and record the weight.
4) Turn on the air conditioner in cooling
mode.
5) Open the valves (Low side)on the charge
set and charge the system with liquid
refrigerant.
6).When the electronic scale displays the
proper weight (refer to the gauge and the
pressure of the low side), disconnect the
charge hose from the 3-way valve’s service
port immediately and turn off the air
conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service
port.
Use torque wrench to tighten the service
port cap to a torque of 18N.m(13.27 ft·lbs).
Be sure to check for gas leaks.
4.6 Procedure when servicing the
indoor unit refrigeration circuit.
1. Collecting the refrigerant into the
outdoor unit
Summary of Contents for MCH2U-18PHH2
Page 3: ...3 MCH4U 36PHH2 WD30 metal plate 118 MCH5U 48PHH2 WE30 metal plate 125...
Page 23: ...23 7 Wiring Diagrams 7 1 Wiring diagram of 1 drive 2 outdoor MCH2U 18PHH2...
Page 24: ...24 7 2 Wiring diagram of 1 drive 3 outdoor MCH3U 27PHH2...
Page 25: ...25 7 3 Wiring diagram of 1 drive 4 outdoor MCH4U 36PHH2...
Page 26: ...26 7 4 Wiring diagram of MCH5U 48PHH2...
Page 31: ...31 PCB board of MCH5U 48PHH2...
Page 32: ...32 IPM board of MCH5U 48PHH2...
Page 44: ...44...
Page 46: ...46 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Page 54: ...54 8 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Page 59: ...59...
Page 61: ...61 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Page 64: ...64...
Page 68: ...68 IPM board for 2 zone 3 zone...
Page 70: ...70 IPM board for 4 zone...
Page 73: ...73 Two ports of the inductance Inductance...
Page 76: ...76 Vs Vcc Vsp FG...
Page 78: ...78...
Page 79: ...79...
Page 81: ...81...
Page 82: ...82...
Page 84: ...84...
Page 85: ...85...
Page 87: ...87...
Page 98: ...98 6 EXV check Disconnect the connectors...
Page 100: ...100 Red Blue Red Yellow...
Page 101: ...101 Brown Orange...
Page 102: ...102 Brown White...
Page 112: ...112 Screws of front panel Screws of right rear panel Screws of front panel...
Page 120: ...120 Screws of front panel Screws of right rear panel Screws of front panel...