background image

3

installation manual

795

514

340

365

287

550

330

Table 2-1

mm

MODEL

A

B

C

D

E

H

REMARK

F

05~07

10

14~16

990

624

366

396

340

965

345

1170

03

Fig.2-2

722

453

302

327

260

555

300

Fig.2-2

Fig.2-3

590

378

400

330

350

900

Fig.2-4

>30cm

/11.81in

>30cm /11.81in

>200cm /78.74in

>60cm

/23.62in

(Wall or obstacle)

Maintain channel

Air outlet

Air inlet

M

P

Air inlet

N

Fig 2.5

2.3   Space of installation and maintenance

(in=mm/25.4)

2.4   Moving and installation

Fig 2.6

>60cm /23.62in

Fix with bolt

Since the gravity center of the unit is not at its physical 

center, so please be careful when lifting it with a sling.

Never hold the inlet of the outdoor unit to prevent it from 

deforming.

Do not touch the fan with hands or other objects.

Do not lean it more than 45, and do not lay it sidelong.

Make concrete foundation accoding to the sepecif-ications of 

the outdoor units.

(Refer to Fig.2-6)

Fasten the feet of this unit with bolts firmly to prevent it from 

collapsing in case of earthquake or strong wind.

(Refer to 

Fig.2-6)

 

3.1   Preparation and Caution

3    INSTALL THE CONNECTING PIPE

Before installation make sure the height difference, the 

length of refrigerant pipe, and the number of the bends 

between the indoor unit and outdoor unit meet the 

following requirements:

Table 3-1

unit:m

The outdoor unit is charged with rating refrigerant amount in 

the factory. Additional charge refers to the table below: 

Table 3-2

liquid tube(mm)

R410A

Ø6.35

Ø9.53

0.022kg/m×(L-5)
0.060kg/m×(L-5)

Model

The type of models

R410A Split type air conditioner 

03/05/07

10/14/16

30m/98.7ft 

20m/65.8ft

20m/65.8ft

 

10m/32.9ft

refrigerant pipe

The length of 

height drop

The max 

NOTE:The number of bends is up to the length of the max 

height drop.Usually for each 10m/32.9ft need a bend. 

NOTE:the table above refer to the liquid tube.

3.2   The Procedure of Connecting Pipes

Connect the indoor unit first, then the outdoor unit.

Bend the tubing in proper way. Do not twist the pipe.

Bend the pipe with thumb

min-radius 100mm/3.94in

Fig 3.1

Put some refrigerant oil on the surfaces of the flare pipe 

and the joint nuts then wrench it for 3~4 rounds with  

hands  before fasten the flare nuts.

Use frozen oil

Fig 3.2

Measure  the  required  length  of  the  connecting  

pipe,  then make it by the following way.

1)

All field piping must be provided by a licensed 

refrigeration technician and must comply with the 

relevant local and national codes.

Prevent let air, dust, or other impurities enter in the pipe 

system during installation.

Insulation pipe shall be used to the gas piping and the 

liquid piping. Otherwise, the condensate may happen.

CAUTION

Summary of Contents for MCCU-03CN1A

Page 1: ...TION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference MCCU 03CN1A MCCU 05CN1A MCCU 07CN1A MCCU 10CN1 MCCU 12CN1 MCCU 16CN1 ...

Page 2: ......

Page 3: ...hen where oil permeates Place where strong electromagnetic waves exist Place where flammable gases or materials exist Place where acid or alkali gases evaporate Other special environments Install the unit where enough space of installation and maintenance is available Install the unit where the air inlet and air outlet are free from obstacles and strong wind Install the unit in a dry and well vent...

Page 4: ... size 2 installation manual 2 1 Installation Place 2 OUTDOOR UNIT INSTALLATION There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can not be reached by strong wind It must be a dry and well ventilating place The support is flat and horizontal and can stand the weight of the outdoor unit And will no additional noise or vibration Your neighborh...

Page 5: ...oor unit and outdoor unit meet the following requirements Table 3 1 unit m The outdoor unit is charged with rating refrigerant amount in the factory Additional charge refers to the table below Table 3 2 liquid tube mm R410A Ø6 35 Ø9 53 0 022kg m L 5 0 060kg m L 5 Model The type of models R410A Split type air conditioner 03 05 07 10 14 16 30m 98 7ft 20m 65 8ft 20m 65 8ft 10m 32 9ft refrigerant pipe...

Page 6: ...d the cables together tightly with binding tapes Pass the bound connecting pipe through the wall sleeve from outside Make sure of the pipe allocation not to damage the copper tubes 3 5 6 7 4 Connect the pipes Expel the air with a vacuum pump or refrigerant Open the service valves of the outdoor unit Check the refrigerant leakage Check all the joints with the leak detector or soap water Cover the j...

Page 7: ...Hi stop valve C D Joints of the connecting pipe to the indoor unit B A D C Check point of indoor unit Check point of outdoor unit 76 cmHg Lo lever Hi lever Charge hose Charge hose Vacuum pump Lo lever Manifold valve Multi meter Pressure meter Fig 5 3 Fig 5 4 Fig 5 5 Loosen and remove the nuts of service valves A and B and connect the charge hose of the manifold valve with the maintenance terminato...

Page 8: ...stion contact your local dealer 1 2 4 3 5 Refer to EMC Directive 2004 108 EC To prevent flicker impressions during the start of the compressor following installation conditions do apply NOTE Disassemble the cover If there isn t a cover on the outdoor unit disassemble the screw from the maintenance board and pull it in the direction of the arrow to remove the protection board Refer to Fig 8 1 Conne...

Page 9: ...rsed the compressor will not start Meanwhile the fault indicator of the outdoor electric control board will light up For details see Outdoor unit wring diagram on the cover plate of the electric control box After shifting the phase sequence power on the unit until the fault indicator goes out and the compressor starts up normally NOTE 10 ELECTRIC WIRE DIAGRAM MCCU 03CN1A RVV 300 500 2X2 5 1x1 5 mm...

Page 10: ...ipeline system is inspected for leakage Check whether the drain is smooth Check whether the heat insulation is perfect Check whether the ground cables are connected correctly Check whether the pipe length and the refrigerant amount are recorded Check whether the supply voltage is equal to the rated voltage of the air conditioner Check whether any obstacles exist at the air inlet outlet of the indo...

Page 11: ......

Page 12: ...16123000A18669 V1 0 ...

Page 13: ...本页不打印 规格 A4 材质 100g双胶纸 更改记录 ...

Reviews: