background image

5

installation manual

CAUTION

Table 5-1

(mm)

Ø6.35/0.25in

8.3/0.327in   8.7/0.343in

Ø9.52/0.375in

12.0/0.472in 12.4/0.488in

Ø12.7/0.5in

15.4/0.606in 15.8/0.622in

Ø15.9/0.626in

Ø19.1/0.725in

18.6/0.732in 19.0/0.748in

22.9/0.902in 23.3/0.917in

R0.4~0.8

45 °±2

90 °     

± 4

A

min

max

Pipe  gauge

Tightening   torque

Flare dimensin A

Flare     shape

97.2

118.6 N.m

(990

1210 kgf.cm)

(630

770 kgf.cm)

61.8

75.4 N.m

49.5

60.3 N.m

(504

616 kgf.cm)

32.7

39.9 N.m

(333

407 kgf.cm)

14.2

17.2 N.m

(144

176 kgf.cm)

Too large torque will harm the bellmouthing and too small will 

cause leakage.  Please determine the torque according to 

Table 5-1.

Expel the air with a vacuum pump

  

3)

(Please refer to its manual for the way of using manifold 

valve)

CAUTION

When the pumping has finished, close the Lo-lever of the 

manifold valve completely and turn off the vacuum pump.

When you have pumped for over 15 minutes, please 

confirm that the indicator of  multimeter is on  -1.0X10

-5

Pa 

(-76cmHg) 

Loosen  and remove the nuts of service valves A and B to 

open service valve A andB completely, then fasten nuts.

Disassemble the charge hose of service valve A, and  

fasten the nut.

Both service valves should be open before test operation. 

Each air conditioner has two service valves of different 

sizes.(Refer to 

Fig 5.4

)

Flare nut

Stopper

Cap

Valve body

Valve stern

5.2   Check the Leakage

Check all the joints with the leak detector or soap water. 

(

Refer Fig 5.5 

as a reference illustration)

in the chart

A......Lo-stop valve

B......Hi-stop valve

C,D..Joints of the connecting pipe to the indoor unit.

B

A

D

C

Check-point of indoor unit

Check-point of outdoor unit

-76 cmHg

Lo-lever

Hi-lever

Charge hose

Charge hose

Vacuum pump

Lo-lever

Manifold valve

Multi-meter Pressure meter

 Fig 5.3

Fig 5.4

Fig 5.5

Loosen and remove the nuts of service valves A and B, 

and connect the charge hose of the manifold valve with 

the maintenance terminator of service valve A.  (Be sure 

that service valves A and B are both closed)

Connect the joint of the charge hose with the vacuum 

pump.

Open the Lo-lever of the manifold valve completely.

Turn on the vacuum pump. At  the beginning of pumping, 

loosen the nut of service valve B a little to check whether 

the air comes in (the sound of the pump changes, and 

the indicator of compound meter turns below zero). Then 

fasten the nut.

5.3   Insulation

Be sure to completely insulate all the exposed parts of the flare 

pipes. 

Incomplete insulation may cause condensate.

In order to prevent faults caused by condensate of the 

refrigerant pipe and drain pipe, perform condensate prevention 

and heat insulation properly. 

If it is forecast that high humidity/temperature environment 

(condensate temperature is over 23

) may exist in the ceiling, 

e.g., inside the ceiling with slab, ceiling which is in the same 

environment as the outdoor air), it is necessary to apply 10mm 

or thicker adiabatic wool (16~20kg/m

2

 ) to the refrigerant pipe 

and the drain pipe in addition to applying the general heat 

insulation materials. Enough heat insulation materials should 

also be applied to the refrigerant joint and the pipe joint.

CAUTION

6.    HEAT INSULATION OF THE PIPE 

6.1  Heat Insulation Of The Pipe 

Summary of Contents for MCCU-03CN1A

Page 1: ...TION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference MCCU 03CN1A MCCU 05CN1A MCCU 07CN1A MCCU 10CN1 MCCU 12CN1 MCCU 16CN1 ...

Page 2: ......

Page 3: ...hen where oil permeates Place where strong electromagnetic waves exist Place where flammable gases or materials exist Place where acid or alkali gases evaporate Other special environments Install the unit where enough space of installation and maintenance is available Install the unit where the air inlet and air outlet are free from obstacles and strong wind Install the unit in a dry and well vent...

Page 4: ... size 2 installation manual 2 1 Installation Place 2 OUTDOOR UNIT INSTALLATION There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can not be reached by strong wind It must be a dry and well ventilating place The support is flat and horizontal and can stand the weight of the outdoor unit And will no additional noise or vibration Your neighborh...

Page 5: ...oor unit and outdoor unit meet the following requirements Table 3 1 unit m The outdoor unit is charged with rating refrigerant amount in the factory Additional charge refers to the table below Table 3 2 liquid tube mm R410A Ø6 35 Ø9 53 0 022kg m L 5 0 060kg m L 5 Model The type of models R410A Split type air conditioner 03 05 07 10 14 16 30m 98 7ft 20m 65 8ft 20m 65 8ft 10m 32 9ft refrigerant pipe...

Page 6: ...d the cables together tightly with binding tapes Pass the bound connecting pipe through the wall sleeve from outside Make sure of the pipe allocation not to damage the copper tubes 3 5 6 7 4 Connect the pipes Expel the air with a vacuum pump or refrigerant Open the service valves of the outdoor unit Check the refrigerant leakage Check all the joints with the leak detector or soap water Cover the j...

Page 7: ...Hi stop valve C D Joints of the connecting pipe to the indoor unit B A D C Check point of indoor unit Check point of outdoor unit 76 cmHg Lo lever Hi lever Charge hose Charge hose Vacuum pump Lo lever Manifold valve Multi meter Pressure meter Fig 5 3 Fig 5 4 Fig 5 5 Loosen and remove the nuts of service valves A and B and connect the charge hose of the manifold valve with the maintenance terminato...

Page 8: ...stion contact your local dealer 1 2 4 3 5 Refer to EMC Directive 2004 108 EC To prevent flicker impressions during the start of the compressor following installation conditions do apply NOTE Disassemble the cover If there isn t a cover on the outdoor unit disassemble the screw from the maintenance board and pull it in the direction of the arrow to remove the protection board Refer to Fig 8 1 Conne...

Page 9: ...rsed the compressor will not start Meanwhile the fault indicator of the outdoor electric control board will light up For details see Outdoor unit wring diagram on the cover plate of the electric control box After shifting the phase sequence power on the unit until the fault indicator goes out and the compressor starts up normally NOTE 10 ELECTRIC WIRE DIAGRAM MCCU 03CN1A RVV 300 500 2X2 5 1x1 5 mm...

Page 10: ...ipeline system is inspected for leakage Check whether the drain is smooth Check whether the heat insulation is perfect Check whether the ground cables are connected correctly Check whether the pipe length and the refrigerant amount are recorded Check whether the supply voltage is equal to the rated voltage of the air conditioner Check whether any obstacles exist at the air inlet outlet of the indo...

Page 11: ......

Page 12: ...16123000A18669 V1 0 ...

Page 13: ...本页不打印 规格 A4 材质 100g双胶纸 更改记录 ...

Reviews: