middle of the bendable pipe. Do not bend the pipe more than three times.
Be sure to use the same insulation materials when you buy the brass pipe.
Bend the tubing in proper way. Do not twist the pipe.
Put some refrigerant oil on the surfaces of the flare pipe and the joint nuts when wrench it for 3~4
rounds with hands before fasten the flare nuts.
Drill a hole in the wall (suitable just for the size of the wall sleeve), then set on the fittings such as
the wall sleeve and its cover.
Bind the connecting pipe and cables together tightly with binding tapes. Pass the bound
connecting pipe through the wall sleeve from outside. Make sure of the pipe allocation not to
damage the copper tubes.
Allowed length of refrigerant pipe and height difference.
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1,
MCCU-10CN1, MCCU-14CN1, MCCU-16CN1:
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1:
Allowed value
Max. actual length of pipe (L)
20m
Max. height difference between
indoor and outdoor unit
Outdoor unit (upper)
10m
Outdoor unit lower (lower)
10m
Summary of Contents for MCCU-03CN1
Page 19: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 19 MCCU 07CN1 MCCU 10CN1 ...
Page 20: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 20 MCCU 14CN1 MCCU 16CN1 ...
Page 23: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 23 MCCU 70CN1 MCCU 105CN1 ...
Page 26: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 26 MCCU 45CN1 ...
Page 31: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 31 MCCU 45CN1 ...
Page 33: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 33 MCCU 105CN1 ...
Page 77: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 77 Hi pressure protection ...
Page 78: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 78 Low pressure protection ...