11. Compressor
11.1 Compressor on and off Control specifications
1.1 When one of the following conditions is met, the compressor stops:
1)
Tr ≤ Trt
;
2) The compressor runs continuously for more than 3 hours (Stop 5 minutes);
1.2 When all the following conditions are met, the compressor starts up:
1)
Tr ≥Trk;
2) Compressor downtime is more than 5min.
★
When 1.1 and 1.2 are not satisfied, the compressor maintains the original state