background image

32801002001                                                                            Specifications subject to change without notice.                                                                                         

21

SETTING STATIC PRESSURE WHEN USING 
THE RG57 WIRELESS CONTROLLER:

The external static pressure should be selected using the wireless 
remote controller (RG57F3(B)/BGEFU1), included with the indoor 
unit, by pointing it toward the indoor unit’s Infrared Receiver 
typically located inside the control box.

1. Before using the service functions of the remote, turn 

OFF

 the 

indoor unit with the remote.

2. Turn off the power to the indoor and outdoor units for 3 minutes.

Turn the power back on.

3. Remove the batteries from the RG57 remote and wait for the

remote screen to clear or press any button and the screen will clear.

4. Reinstall the batteries.
5. Within 30 seconds of replacing the batteries, simultaneously press

MODE

 and 

TIMER ON

 for five (5) seconds. You are now in the

SERVICE FUNCTION

 mode – and the remote display reads 

F1

.

6. Press the 

DOWN

 arrow in the center of the remote (labeled

TEMP

) to display 

E9

.

7. Press        or       to select 

E9

.

8. Press 

MODE

 to set the airflow rate in the range of 1~4.

9. Press 

TIMER ON

 to confirm.

10. Remove the remote controller battery, and then re-insert the battery

after the remote controller screen goes blank. The remote controller

exits the 

MODIFICATION

 mode. After you power 

OFF

 the unit,

power the unit 

ON

 again and the unit retains the setting value. 

Fig. 65 — RG57 Remote Controller

FP

Activate/Disable freeze
protection function

ON/OFF 

Turns the unit on or off

MODE

Scrolls through operation 

modes as follows: 

AUT O

 

 

COOL

 

 

DR Y

 

 

HEA T

 

 

FAN

FAN/SLC

 

Selects fan speeds in the
following order: 

AUT O   LOW 

 

MED 

 HIGH

SLEEP

 

Saves energy during 

Hold down this button for
2 seconds to activate the
Silence function.

sleeping hours

TURBO 

Enables unit to reach 
preset temperature in

shortest possible time 

TEMP

Increases temperature in 

O

1 F (1

°C) increments

Max. temperature is 

 

O

86 F

TEMP

Decreases temperature in 

O

1 F    (1

°C) increments

Min. temperature is 

 

O

62 F 

TIMER ON

 

Sets timer to turn unit on 

 

 

TIMER OFF 

 

Sets timer to turn unit off 

SWING/DIRECT 

Starts and stops up-down
airflow louver movement 

LED

Turns indoor unit s LED display on and off.

,

FOLLOW ME

Temperature sensing 
and room temperature
display button

   SELF CLEAN

Starts and stops
self clean feature

O N/O F F

T E MP

FP

TIMER
  ON

TIMER
  OFF

MODE

FAN/SLC

SLEEP

TURBO

SWING

DIRECT

CLEAN

LED

FOLLOW

If you are sensitive to light when you go to 
sleep, you can press the LED button to turn 
off the LED display on the indoor unit. Press 
the button again to turn it back on   

NOTE:

 Press and hold

      and        buttons 
together for 3 seconds to
alternate the temperature 
display between the 

O

O

C &  F scale

Summary of Contents for DLFLAA

Page 1: ...work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit Consult local building codes a...

Page 2: ...allation parts and accessories to install the system Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Keep the installation manual in a safe p...

Page 3: ...84 11 8 299 13 3 339 3 0 75 2 5 64 4 9 124 6 8 174 1 7 44 A HEIGHT 48 1 1222 C WIDTH 19 7 501 4 8 121 2 4 61 6 7 171 2 2 57 D DUCT 18 2 462 E DUCT 10 3 262 B DEPTH 21 1 535 0 8 21 0 5 13 0 6 16 18 4...

Page 4: ...med according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installation must be performed in accordance with the requirement...

Page 5: ...t is installed over a finished ceiling and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow as an alt...

Page 6: ...t 5 Install the drain lines Fig 7 Vertical Upflow Installations Fig 8 Horizontal Right Installations NOTE For a horizontal right installation secondary condensate pan field supplied must be installed...

Page 7: ...d drain pan assembly 9 Reinstall the pipe temperature sensor in its original position Attach the room temperature sensor to the evaporator output pipe protection sleeve Fig 15 Reinstall the Pipe Tempe...

Page 8: ...uipped with the electric auxiliary heat module please check the electric auxiliary heat module specification that is compatible with the unit to avoid unnecessary consequences caused by improper match...

Page 9: ...into the opening made by removal of the sheet metal cover s Ensure the two support rod ends are on the opposite bulkhead Fig 24 Insert Heating Module 5 Use the 3 screws 6 screws for 15K or 20K remove...

Page 10: ...quirements and local codes see Table 6 on page 11 Choose the power cord and the power cord installation location see Figure 30 Each circuit breaker group needs to connect to the power input line Where...

Page 11: ...do not have a 90 degree elbow and 10ft 3m of main duct to first branch takeoff may require internal acoustical insulation lining As an alternative fibrous ductwork may be used if constructed and insta...

Page 12: ...ood 2 Use a 2 5in 65mm core drill to drill a hole in the wall Make sure the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 0 5in 1...

Page 13: ...g an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating material c Place flare...

Page 14: ...nder to prevent kinking or damaging the tubing 6 After connecting the copper pipes to the outdoor unit wrap the power cable signal cable and the piping together with binding tape NOTE While bundling t...

Page 15: ...ost positive way of assuring a system is free of air and moisture see Fig 49 NOTE DO NOT add a filter line drier Fig 49 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should b...

Page 16: ...it would lose power A disconnect switch is not required on the indoor unit side on the wiring between the outdoor and indoor unit A 3 pole disconnect purchased separately may be used for extra protect...

Page 17: ...e is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 power stranded with a ground Communication Wiring A separate 2 wire cable stranded shielded copper conductor with...

Page 18: ...0 5 0 20 120 36 5 0 42 250 48 5 0 65 400 3 S 1 L1 2 L2 208 230 1 60 Power Supply Main 1 L1 208 230 1 60 2 L2 3 S 1 L1 2 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indo...

Page 19: ...Indoor Unit Control Box Sizes 36 48 LED Display The control displays active faults codes on the LED display When the control displays the fault code and the LED flashes quickly there is something wro...

Page 20: ...nnected b Turn off the power to the indoor and outdoor units for 3 minutes c Turn the power back on Wait 1 minute and check the 24 volt Interface digital display If the display reads 00 then proceed I...

Page 21: ...troller exits the MODIFICATION mode After you power OFF the unit power the unit ON again and the unit retains the setting value Fig 65 RG57 Remote Controller FP Activate Disable freeze protection func...

Page 22: ...1 400 1 310 1 215 1 105 950 825 Low 1 525 1 450 1 372 1 280 1 190 1 074 935 785 650 36 SP1 High 1 335 1 270 1 165 1 062 950 810 645 450 240 Medium 1 185 1 100 990 845 685 520 335 Low 1 020 915 775 60...

Page 23: ...Pressurein WC High Medium Low SP4 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta cPressurein WC High Medium Low SP1 0 200 400 600 800 1 000 1...

Page 24: ...M Sta cPressurein WC High Medium Low SP2 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta c Pressurein WC High Medium Low SP3 0 200 400 600 800...

Page 25: ...conditioner Turn off the main power switch and reinstall the test cover NOTE If the unit malfunctions or does not operate according to your expectations please refer to the Troubleshooting section of...

Page 26: ...FF E0 Indoor unit EEPROM parameter error 2 times OFF E1 Indoor outdoor unit communication error 4 times OFF E3 The indoor fan speed is operating outside of the normal range 5 times OFF E4 Indoor room...

Reviews: