Service manual
45
No
Yes
Yes
No
Yes
Yes
No
No
No
Yes
13.1.8
Display LED
STATUS
P1
Over voltage or too low voltage protection
13.1.9
Display LED
STATUS
P2
Compressor top protection against temperature
Off: 115
゜
C; On: 100
゜
C
Is connection to connector good?
Is the wires to compressor right?
Check the inverter module,
If some component
cracked or damaged?
Is it breakdown between P-N,P-U,P-V;N-W,N-U,N-V
At inverter module
Check compressor
Inverter module is defective
Repair connector
Is the power supply right?
Check the outdoor power board
Replace outdoor main PCB.
Yes
Check the voltage between P and N on inverter
module. Is it about 380V?
Test the outdoor power supply board again.
Inverter module damaged, replace it.
Summary of Contents for AAC-18ISCH
Page 4: ......
Page 16: ...Service manual 12 5 Refrigerant cycle diagram...
Page 20: ...Service manual 16 7 1 5 Indoor main PCB Inverter Eco...
Page 21: ...Service manual 17 7 1 6 Outdoor main PCB Inverter Eco...
Page 22: ...Service manual 18 7 2 Wiring diagram 7 2 1 MSH 18HRDN1...
Page 23: ...Service manual 19 7 2 2 MSC 18HRIN1...
Page 24: ...Service manual 20 7 2 3 MSE 09HRIN2 MSE 12HRIN2...