FRONT VIEW

 REAR VIEW

PDCOOL-1015RA CONNECTIONS, CONTROLS AND INDICATORS 

1

1

2

50CFM BLOWER: This blower will turn on at 87° F (30.5° C) and run proportionately 

(speed increases with temperature) from 87° F (30.5° C) to 95° F (35° C). At 95° F and above, the 

blower will run at full speed. The blower will stop running at 85° F (29.4° C). 

C14 IEC POWER CORD INLET: 120V/60Hz power inlet. Plug supplied power cord from AC source 

into this inlet.

3

15 AMP CIRCUIT BREAKER: Provides protection for both front and rear outlets.

4

TEN NEMA 5-15R OUTLETS. 

5

SURGE STATUS OUTPUT DRY CONTACT: This dry contact will close if both stage 1 and 2 surge is

compromised.  

6

TEMPERATURE PROBE CONNECTION: 10 foot temperature probe provided.

7

GROUND/BOND STUD.

3

7

2

4

5

6

PDCOOL-1015RA

Reset

A blue LED will illuminate when the blower is receiving power.

120V - 60Hz - TOTAL 12A

Summary of Contents for PDCOOL-1020RK

Page 1: ...h static pressure to maintain airflow Multi stage surge protection with surge status notification Thermal sensing with proportional blower speed Thank you for purchasing the PowerCool Series component...

Page 2: ...z l appareil de la source d alimentation avant l entretien de tout quipement connect Do not overload the wall outlet where this device is being connected Do not overload this device Ensure the total l...

Page 3: ...mal management If the equipment being cooled is vented no blank panel is required Install the PDCOOL at the top of the rack and secure the temperature probe at the highest available location The PDCOO...

Page 4: ...SWITCH GUARD TWO STAGE SURGE SUPPRESSION STATUS INDICATORS NEMA 5 20R POWER OUTLET C20 IEC POWER CORD INLET 120V 60Hz power inlet Plug supplied power cord from AC source into this inlet 6 GROUND BOND...

Page 5: ...SSION STATUS INDICATORS NEMA 5 15R POWER OUTLET C14 IEC POWER CORD INLET 120V 60Hz power inlet Plug supplied power cord from AC source into this inlet 6 GROUND BOND STUD 7 TEN NEMA 5 15R OUTLETS 8 SUR...

Page 6: ...he key for security Stage One Indicator Stage Two Indicator Status On On Full Protection Off On Stage One Compromised Off Off Load Unprotected or Power Off C20 IEC POWER CORD INLET 120V 60Hz power inl...

Page 7: ...9 4 C C14 IEC POWER CORD INLET 120V 60Hz power inlet Plug supplied power cord from AC source into this inlet 3 15 AMP CIRCUIT BREAKER Provides protection for both front and rear outlets 4 TEN NEMA 5 1...

Page 8: ...ce THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO T...

Reviews: