Page 6
COMPONENT COOLER AND POWER DISTRIBUTION
PROTECTION
SURGE
ON
OFF
PDCOOL-1020RK
Reset
FRONT VIEW
REAR VIEW
PDCOOL-1020RK CONNECTIONS, CONTROLS AND INDICATORS
1
1
2
3
5
2
3
50CFM BLOWER: This blower will turn on at 87° F (30.5° C) and run proportionately
(speed increases with temperature) from 87° F (30.5° C) to 95° F (35° C). At 95° F and above, the
blower will run at full speed. The blower will stop running at 85° F (29.4° C).
KEYED POWER SWITCH: Using provided key, you can turn the power on/off and remove the key
for security.
Stage One Indicator Stage Two Indicator Status
On On Full Protection
Off On Stage One Compromised
Off Off Load Unprotected or Power Off
C20 IEC POWER CORD INLET: 120V/60Hz power inlet. Plug supplied power cord from AC source
into this inlet.
6
20 AMP CIRCUIT BREAKER: Provides protection for both front and rear outlets.
7
TEN NEMA 5-20R OUTLETS.
8
SURGE STATUS OUTPUT DRY CONTACT: This dry contact will close if both stage 1 and 2 surge is
compromised.
9
TEMPERATURE PROBE CONNECTION: 10 foot temperature probe provided.
10
GROUND/BOND STUD.
6
10
5
7
8
9
TWO STAGE SURGE SUPPRESSION STATUS INDICATORS:
A blue LED will illuminate when the blower is receiving power.
120V - 60Hz - TOTAL 16A