background image

7

The flame sensing rod must be positioned as shown in Figure 3  so that the Electronic

Control will detect a proper flame.

Both the spark and flame rods are current carrying conductors and, along with their

connecting wires, must be kept free of contact with conductive metal parts of the burner. Rod
insulators and wire insulators should be clean, dry and free of cracks.

Both the spark and flame rods are made from heat resistant alloys and can be expected to

have a long service life. They should be routinely inspected, however, for corrosion or loss of
metal.

____________________________

Should replacement or service be required, valve manufacturer's instructions must be

followed as outlined in their information sheet.

Outlet pressure settings must be checked while the gas is flowing.

To adjust outlet pressure, remove the seal cap for access to the adjusting screw. Turning

the screw clockwise will increase outlet pressure, counter clockwise will decrease outlet
pressure.

____________________________

The Midco RE4400DS is supplied with two timers to provide high fire purge and low fire

start.  With power applied to L1 and L2 the blower motor starts.  Once the blower motor
starts the blower air switch closes.  24 Volt power is applied to the air damper actuator and
prepurge timer.  The air damper actuator begins to open the air damper to provide a high fire
purge.  After 45 seconds the air damper actuator begins to close.  24 Volt power is then
applied to the Honeywell S87K DSI Ignition control module.  The S87K DSI Ignition control
module also provides additional prepurge for 30 seconds.  Once the S87K DSI Ignition
control module completes its prepurge 24 volts is applied to the Combination gas valve and
internal ignition transformer.  If flame is proven (minimum 2 DC Micro amps) the burner will
continue in the run mode.  The 2 to 10 Volts DC temperature control will then begin to
modulate the air damper actuator to provide the proper combustion air for the burner.  The
feedback signal from the air damper actuator will drive the spring return gas valve actuator to
provide the correct gas flow for the burner.  Refer to Table 3 for the correct maximum fire
manifold pressure settings.

If the burner lights and then loses the DC micro Amp flame signal it will retry to ignite after
completing an additional prepurge cycle.  If the burner fails to reignite power will need to be
turned off and reapplied after 30 seconds.

For startup information see section X.

____________________________

The S87K is a low voltage, solid state, direct spark ignition control module for gas-fired

furnaces, boilers and heating appliances. UL Listed models are only available with a pre-
purge timer.  The S87K controls the gas valve, monitors the main burner flame and
generates a high voltage for spark ignition.

The S87K uses separate electrodes for spark ignition and flame sensing.  Includes a 30

second (minimum) delay for use with system pre-purge. 

For operation characteristics, maintenance, and service procedures, refer to

manufacturer's literature provided with burner, or contact your Honeywell dealer.

____________________________

Startup instruction for RE 4400DS HTD

1.  Set the operating control to off or thermostat below room temperature.
2.  Turn manual gas cock on.
3.  Turn burner power on.
4.  Set operating control to ON or thermostat to call for heat. Wait 75 seconds, if the 

burner has failed to light, or if burner lights then goes out, the system will go into 
safety lockout. De-energize the system by setting operating control to off or 
thermostat below room temperature for at least 30 seconds to reset the system.
Repeat step 4 for restart.

5.

The Belimo Actuator controls the firing rate of the burner by providing a signal to 
terminal 3 on the actuator. The actuator has stops (set screws), which have been 
pre-set to 20 MBH (0.02” W.C. manifold pressure, 2 Volts DC signal input) at low fire 
and 400 MBH at maximum fire (4.5” W.C. manifold pressure, 8 Volts DC signal 
input) at zero back pressure. The regulator on the combination valve has been set to 
high fire and should not need to be adjusted. The “Modulating Gas Valve” (butterfly 
valve which is attached to the spring return actuator) will vary the amount of gas flow 
into the burner.

Part 2 Service 

Part 2

Service

VII

Valve Train

VIII  

Sequence of

Operation

IX

Electronic

Control

X Start 

Up 

VI

Electrodes
Continued

Summary of Contents for Economite RE4400DS

Page 1: ...ry to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If y...

Page 2: ...ion chamber and to permit burner removal or as recommended by the equipment manufacturer CAUTION In no case should the burner tube be allowed to extend into the chamber because high combustion chamber...

Page 3: ...ximum firing rate of the burner the gas supply piping must be sized to provide a minimum pressure of 7 0 W C Natural for 400 MBH to the inlet of the combination redundant valve when the burner and all...

Page 4: ...rop however the size must be sufficient to deliver burner rating pressure CAUTION High gas pressure supply lines require the proper pressure reducing regulators Install a high pressure regulator of th...

Page 5: ...Do not purge into the gas utilization equipment 3 To purge the gas utilization equipment and chimney of any accumulated gases turn main Manual Gas Cock OFF turn burner power on and set operating cont...

Page 6: ...r by checking the flue gases with an ORSAT or similar combustion testing instrument The carbon monoxide content should conform to local codes or in their absence to the level specified in the United S...

Page 7: ...o provide the correct gas flow for the burner Refer to Table 3 for the correct maximum fire manifold pressure settings If the burner lights and then loses the DC micro Amp flame signal it will retry t...

Page 8: ...r reduce the air vary the alignment between the damper and the inlet ring Minimum air shutter adjustment can be done by adjusting the three 8 18 screws on the inlet ring see Figure 5 To increase or de...

Reviews: