Midco economite RE4400B Installation And Service Instructions Manual Download Page 15

Part 3 Trouble Chart

TROUBLE CHART

Make sure the thermostat and operating controls are calling for heat. 

CAUTION:  If a test indicates an electrical component may be defective,

before  replacing it, make sure that its associated wiring is not at fault.

ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED BELOW.

I.

MOTOR WILL NOT RUN

A.

Confirm 120V between strip terminals 

L1

and 

L2 

and verify the circuit polarity and 

electrical ground between strip terminal 

L1 

and burner Ground.

B.

Check for 120V between strip terminals 

L1 

and 

L2

.

1.

No voltage, open circuit in operating controls.

2.

Voltage present, motor is defective.

II.

MOTOR RUNS CONTINUOUSLY, PILOT WILL NOT LIGHT

A.

Confirm that ALL Main Manual Shut-Off Valves are in the 

ON 

position.

B.

After the pre-purge, if the pilot flame is not proven within the pilot flame re-
re-establishing period, or if the proof of flame is lost during the burner run and the 
pilot is not re-established after the pre-purge, the Ignition Control Module will 

lock 

out.

To reset the control for restart, de-energize the Ignition Control Module  by 

setting the operating control to 

OFF

or thermostat below room temperature for at 

least 60 seconds.

C.

Clogged pilot orifice.

D.

Pilot regulator mis-adjusted 
or defective.

E.

Defective spark electrode or 
Ignition Control Module.

F.

Defective high tension wire.

G. Wrong pilot orifice.
H.

Defective pilot valve.

I.

Pilot air tube clogged.

J.

Incorrect spark gap.

K.

Pilot regulator vent clogged.

L.

Defective blower air switch.

M. Slow motor.
N.

Step down transformer is defective.

III

PILOT LIGHTS, NO MAIN FLAME

A.

Poor pilot flame adjustment.

B.

Clogged pilot air tube.

C.

Defective flame sensing rod or wire.

D.

Flame sensing rod mis-located.

E.

Pilot regulator vent clogged.

F.

Defective Ignition Control Module.

G. Defective main gas valve.
H.

Low gas pressure.

I.

Grossly mis-adjusted main gas and air.

15

Part 3

Continued

Trouble Chart 

I

Motor Will

Not Run or Motor
Runs  in Repeated

Cycles

II 

Motor Runs

Continuously, But

No Flame

III 

Pilot Lights,

No Main Flame

Summary of Contents for economite RE4400B

Page 1: ...850BA RE4700BA RE4400B RE4400BA Gas Burners BURNER MODEL BILL OF MAT L NUMBER SERIAL CODE WIRING DIAGRAM FOR SERVICE CONTACT Name Address Phone Date of Installation Do not store or use gasoline or oth...

Page 2: ...Listed 6 See Section XII of Operational Sequence CAUTION The ECONOMITE Models RE4850BA RE4700BA RE4400B and RE4400BA Burners are not intended for outdoor installation and must be protected from excess...

Page 3: ...et at least 1 short of the inside surface because high combustion chamber temperatures will cause premature pilot electrode burner tube and sleeve deterioration WARNING BURNER MUST BE MOUNTED IN ORIEN...

Page 4: ...between the hood or regulator and the combustion air supply see Figures 3 and 4 In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than th...

Page 5: ...ir furnace fans or boiler pumps to a combination limit control and switch Set the thermostat heat anticipator for the total current draw handled by the thermostat The current draw of the ECONOMITE 24V...

Page 6: ...in any position the main regulator if equipped should be mounted upright and in a horizontal run of pipe CAUTION Because it is difficult to accurately control pressure during supply pipe leak testing...

Page 7: ...7 Part 1 Installation Continued Part 1 Installation RE4850BA UL Valve Train Assembly 24VAC Figure 5 Piping Diagram Continued...

Page 8: ...low CAUTION Cover plates guards and enclosures must be maintained in place at all times except during maintenance and service 1 Check the burner piping and valves for gas leaks by applying a weak liqu...

Page 9: ...TE AND BASED ON 0 OVERFIRE PRESSURE AT SEA LEVEL 2 4 2 5 2 7 2 8 2 4 3 9 3 3 2 7 2 2 3 3 0 15 0 688 0 563 0 500 0 422 0 422 0 358 0 358 0 358 0 358 0 290 0 688 3 5 3 1 2 7 2 8 2 4 2 8 3 15 2 4 2 6 4 3...

Page 10: ...associated controls 11 Perform the following final adjustments for combustion and flue gas temperature Take the flue gas samples and temperature immediately ahead of the draft control A The flue gas t...

Page 11: ...trols If trouble occurs contact the installing contractor service agency or fuel supplier See front cover DANGER Be sure that the main and pilot manual Shut Off Valves are closed and the burner power...

Page 12: ...e will arc to the inside of the 3 8 Tee pilot See Figure 7A and 7B The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition Control Module will detect a proper flame...

Page 13: ...er to the literature provided with the power burner For startup information see section VIII For operation characteristics maintenance and service procedures refer to manufacturer s literature provide...

Page 14: ...ction X Motor Blower Interlock LIGHTING INSTRUCTIONS 1 SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM TEMPERATURE 2 TURN MANUAL GAS COCK ON 3 TURN BURNER POWER ON 4 SET OPERATING CONTROL TO ON...

Page 15: ...nd the pilot is not re established after the pre purge the Ignition Control Module will lock out To reset the control for restart de energize the Ignition Control Module by setting the operating contr...

Page 16: ...16 Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 1201 tel 773 604 8700 fax 773 604 4070 web www midco intl com email sales midco intl com 8471 24 Printed in USA...

Reviews: