Midco economite RE4400B Installation And Service Instructions Manual Download Page 10

7.

To make a preliminary setting of the burner input, determine the manifold gas pressure 
required from Table 3 and adjust the Main Gas Pressure Regulator accordingly. See 
Section XI.

8.

To determine the firing rate for NATURAL gas, accurately time test dial for the number 
of seconds for one revolution and use the following formula.  All other gas utilization 
equipment must be off.

3600 x test dial size x BTU value

= BTU/Hr.

No. of seconds for one rev. test dial

Then divide by 1,000 for MBH value.  

Example:

3600 x 1 x 1000   

= 360,000 BTU/HR  =  360 MBH

10 

9.

Check the operation of the burner; start and stop it several times with the thermostat 
or operating control.

10. With the burner running, check the operation of all limit and associated controls.
11. Perform the following final adjustments for combustion and flue gas temperature. Take the 

flue gas samples and temperature immediately ahead of the draft control.
A.

The flue gas temperature should be above 325°F but not exceeding 550°F. 
Excessive flue gas temperatures will result in low efficiencies. Low flue gas 
temperature may cause excessive condensation.  Reset gas input, if necessary, to 
adjust stack temperature.

B.

Make the final setting of the combustion air shutter by checking the flue gases 
with an 

ORSAT or

similar combustion testing instrument. The   carbon monoxide 

content  should conform to local  codes, or in their absence, to the level specified 
in the United States or Canadian Standard referenced on the front cover of this 

10

Part 1 

Installation 

Continued

Part 1 Installation

VIII

Initial Start-

up /Adjustment

Continued

Figure 7A:

General Assembly for RE4850BA, RE4700BA and RE4400BA 

Summary of Contents for economite RE4400B

Page 1: ...850BA RE4700BA RE4400B RE4400BA Gas Burners BURNER MODEL BILL OF MAT L NUMBER SERIAL CODE WIRING DIAGRAM FOR SERVICE CONTACT Name Address Phone Date of Installation Do not store or use gasoline or oth...

Page 2: ...Listed 6 See Section XII of Operational Sequence CAUTION The ECONOMITE Models RE4850BA RE4700BA RE4400B and RE4400BA Burners are not intended for outdoor installation and must be protected from excess...

Page 3: ...et at least 1 short of the inside surface because high combustion chamber temperatures will cause premature pilot electrode burner tube and sleeve deterioration WARNING BURNER MUST BE MOUNTED IN ORIEN...

Page 4: ...between the hood or regulator and the combustion air supply see Figures 3 and 4 In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than th...

Page 5: ...ir furnace fans or boiler pumps to a combination limit control and switch Set the thermostat heat anticipator for the total current draw handled by the thermostat The current draw of the ECONOMITE 24V...

Page 6: ...in any position the main regulator if equipped should be mounted upright and in a horizontal run of pipe CAUTION Because it is difficult to accurately control pressure during supply pipe leak testing...

Page 7: ...7 Part 1 Installation Continued Part 1 Installation RE4850BA UL Valve Train Assembly 24VAC Figure 5 Piping Diagram Continued...

Page 8: ...low CAUTION Cover plates guards and enclosures must be maintained in place at all times except during maintenance and service 1 Check the burner piping and valves for gas leaks by applying a weak liqu...

Page 9: ...TE AND BASED ON 0 OVERFIRE PRESSURE AT SEA LEVEL 2 4 2 5 2 7 2 8 2 4 3 9 3 3 2 7 2 2 3 3 0 15 0 688 0 563 0 500 0 422 0 422 0 358 0 358 0 358 0 358 0 290 0 688 3 5 3 1 2 7 2 8 2 4 2 8 3 15 2 4 2 6 4 3...

Page 10: ...associated controls 11 Perform the following final adjustments for combustion and flue gas temperature Take the flue gas samples and temperature immediately ahead of the draft control A The flue gas t...

Page 11: ...trols If trouble occurs contact the installing contractor service agency or fuel supplier See front cover DANGER Be sure that the main and pilot manual Shut Off Valves are closed and the burner power...

Page 12: ...e will arc to the inside of the 3 8 Tee pilot See Figure 7A and 7B The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition Control Module will detect a proper flame...

Page 13: ...er to the literature provided with the power burner For startup information see section VIII For operation characteristics maintenance and service procedures refer to manufacturer s literature provide...

Page 14: ...ction X Motor Blower Interlock LIGHTING INSTRUCTIONS 1 SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM TEMPERATURE 2 TURN MANUAL GAS COCK ON 3 TURN BURNER POWER ON 4 SET OPERATING CONTROL TO ON...

Page 15: ...nd the pilot is not re established after the pre purge the Ignition Control Module will lock out To reset the control for restart de energize the Ignition Control Module by setting the operating contr...

Page 16: ...16 Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 1201 tel 773 604 8700 fax 773 604 4070 web www midco intl com email sales midco intl com 8471 24 Printed in USA...

Reviews: