VI Piping

CAUTION: The available gas

pressure should be within the lim-
its shown in the SPECIFICATIONS
section. Excessive pressure will
damage Combination Valve and
Regulator. If the supply pressure
exceeds the 14.0" W.C. maximum,
a suitable intermediate main reg-
ulator must be installed ahead of
the Main Manual Shut-Off Valve
shown in Figure 6.

The burner gas supply piping should

branch off from the main line as close
to the gas meter as possible. Do not
connect to the bottom of a horizontal
section. Use new black pipe and mal-
leable fittings free of cutting and
threading burrs or defects.

Provide a sediment trap, union and 

1

/

8

" pressure tap in piping close to burner as shown in Figure 6.

Use pipe joint compound approved for use with Liquid Petroleum Gases.

Piping must comply with local

codes.

To obtain the maximum firing

rate of 225 MBH, the NATURAL

and PROPANE gas supply piping
must be sized to provide minimum
of 5.0" W.C. pressure to the inlet of
the Combination Valve when the
burner and all other gas utilization
equipment are on.

CAUTION:  Because it is

difficult to accurately control
pressure during supply pipe

leak test, it is recommended that the Combination Valve be disconnected. Exposing the
Combination Valve to a pressure over 1/2 PSIG (14.0" W.C.) will damage the valve and
void all warranties.

DANGER: Explosion hazard.

Do not use oxygen for pressure testing.
An explosion could occur during initial start-up.

If the burner piping must be rearranged because of space limitations, be sure to carry out the

general arrangement shown in Figure 6. Install the Combination Valve in any position except up-
side down.

When the burner is installed in jacketed equipment, it is recommended that the Combination

Valve be left adjacent to the burner within the vestibule and the Main Manual Shut-Off Valve be
installed outside.

Standard burners are approved for use with NATURAL or PROPANE gas only, and should be used
only with the gas specified on rating plate.

A Standard Model DS24A Economite is shipped ready for NATURAL gas. As shipped, it is field

convertible to PROPANE gas, see Table 3.

As shipped, the installed NATURAL gas spud has a .218 diameter orifice size for an input

capacity range of approximately 105 to 150 MBH. Spare spuds are included in a spare spud bag
(stamped with inch diameter) for other capacity ranges and/or conversion to PROPANE, see Table 3.

The Combination Valve Gas Pressure Regulator is set to provide 2.0" W.C. manifold gas pres-

sure for minimum spud input and the combustion air shutter is set for maximum spud input, 32
turns from full closed to provide a lean gas/air mixture for initial start-up.

If a standard NATURAL gas ECONOMITE DS24A is to be used with PROPANE gas, affix the

PROPANE label from the spare spud bag over the NAT designation on the rating plate and install
the appropriate size main spud as detailed below.

If the required firing rate does not fall within the range of the installed spud, or if converting to

PROPANE gas, select the correct capacity range from Table 3 and if so indicated, the spud with
the correct orifice size (stamped with inch diameter) from the spare spud bag. If the required fir-
ing rate is at the minimum of a capacity range, select the next lower range spud.

To change the main spud, turn off the Main Manual Shut-Off Valve and burner power, remove

the backplate, disconnect the factory installed union located between Combination Valve and
manifold slide plate and pull out curved manifold pipe. Unscrew the installed main spud from the
end of the curved manifold pipe and install the selected main spud, making sure to reuse the
fiber spud gasket. Reassemble burner in reverse order.

Pipe 

Size

1

/

2

3

/

4

1

1

1

/

4

130

200
225

90

145
190
225

60

100
130
205
225

50

80

105
165
195

60

80

125
150

225
225

Type

of Gas

NATURAL
PROPANE

NATURAL
PROPANE
NATURAL
PROPANE

NATURAL

Approx. Capacity-MBH

Length of Pipe

Table 2: Supply Pipe Capacities in MBH

5

10

20

40

60

100

Figure 6: Piping Connections

VII Main Gas Spud

Summary of Contents for Economite DS24A

Page 1: ...ch hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions is not followed exactly a fi...

Page 2: ...0 square inches of the total input rating of all gas utilization equipment in the confined space One grille should be located within 12 inches of the ceiling the other within 12 inches of the floor If...

Page 3: ...zzle ribbon is free of for eign materials and also that the electrodes have not been damaged or displaced see Figure 7 WARNING The chimney shall be inspected for unsafe conditions such as deteriorat e...

Page 4: ...e sure to hook up to a permanently live circuit Provide a fused on off disconnect switch carrying a minimum 3 amp fuse The frame of the burner must be well grounded A terminal is provided in the contr...

Page 5: ...OPANE gas only and should be used only with the gas specified on rating plate A Standard Model DS24A Economite is shipped ready for NATURAL gas As shipped it is field convertible to PROPANE gas see Ta...

Page 6: ...or capacity rating of the gas utilization equipment Refer to Section VII Main Gas Spud and Table 3 5 RESET the Electronic Control by setting the operating control to OFF or the thermostat below room t...

Page 7: ...ng and shut off procedure refer to CONSUMER INSTRUCTIONS or to the instruction plate mounted on the burner DANGER Be sure that the Main Manual Shut Off Valve Combination Valve and Burner Power Switch...

Page 8: ...stment an overfire condition could result when pressure returns to normal particularly if the regu lator adjustment screw is bottomed out ALWAYS confirm that at least the minimum rated gas pressure is...

Page 9: ...OR REPAIR WARNING If PROPANE gas is used and the burner is located in a base ment crawl space or confining space contact your gas supplier about installing a GAS LEAK warning device PROPANE gas is hea...

Page 10: ...ol b Between Electronic Control high voltage terminal and Spark Electrode Wire insert head of 8 x 3 4 or longer round head screw into snap terminal inside right angle rubber boot No spark broken wire...

Reviews: