I n s t a l l a t i o n a n d u s e r m a n u a l
H P 1 0 0 0 / 1 4 0 0 G r e e n
V e r s i o n : 0 1 / 2 0 1 9
P a g e
2 2
/ 3 2
H
E
A
T
P
U
M
P
M
I
C
R
O
W
E
L
L
H
P
Parameter Table
NO.
Content
Adjust range
Step length
Default
P0
Water pump running way
0
:
Continuation
1
:
Water temp control
2
:
micro
1
0
P1
Time setting ( only available when
the water pump running way is
set to “2”
10 ~ 120 min
5 min
60 min
P2
Compressor continuously running
time in defrosting mode
30 ~ 90min
1min
35 min
P3
Defrosting start temp
-17 ~ 0
℃
1
℃
-7
℃
P4
Defrosting running time
1 ~ 12min
1min
12 min
P5
Defrosting quit temp
8 ~ 30
℃
1
℃
13
℃
P10
Compressor speed control
0
:
Auto
,
1
:
Manual
1
0
P12
Electronic expansion valve
overheat level
(
heating
)
-10 ~ 20
1
3
P13
Electronic expansion valve
overheat level
(
cooling
)
-10 ~ 20
1
5
P14
Electronic expansion valve
manual/auto
0
:
Auto
,
1
:
Manual
1
0
P15
Electronic expansion valve
openning setting
(
heating
)
50 ~ 240
2P
175
(
H5
)
P16
Electronic expansion valve
openning setting
(
cooling
)
50 ~ 240
2P
175
(
H5
)
P20
Power off memory function
0 — NO
,
1 — YES
1
1
Running status checking
Press”
” for 5 seconds, a sound of “Di” can be heard and it will enter into running status
checking, at this time, the display alternately shows status point “C0” and its corresponding value.
Change status pointer through”
” and “
”, the corresponding value also changes with it.
Press “
” can quit “running status checking” mode