background image

 WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S  MANUAL 

21

Summary of Contents for DRY 300 PLASTIK

Page 1: ...ИНСТРУКЦИЯ Microwell DRY500 Plastik ...

Page 2: ...MODEL DRY 300 400 500 PLASTIK WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL ...

Page 3: ...board l Do not place any objects onto the device l When you do not intend to use the device for a longer time switch off the circuit breaker WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL Thank you for your decision to purchase our device Please read this user manual carefully before switching on the device Please keep the instructions in this practical guide for your quick know how We do n...

Page 4: ...the built in humidistat in the dehumidifier is set for a higher requested humidity value than the remote humidistat If the built in humidistat was set for a lower value than the remote humidistat it would take over and the control of the dehumidifier would not react to the signals from the remote humidistat Therefore it is best to set the built in humidistat to the value of 70 RH or more The built...

Page 5: ... of the fan In such case there are 2 black plastic boxes or casings on the dehumidifier electrobox One is for EBERLE connection another is external thermostat connection This is 230V 5A contact a phase is sent out of a dehumidifier which must be connected to a switching no current contact of an external third party thermostat When heating is required third party thermostat returns this phase back ...

Page 6: ......

Page 7: ...culation into and from the dehumidifier This requires the actual unit placement appropriately into the swimming pool hall respecting basic prerequisites of air circulation and air flow It is strictly forbidden to install the unit just below the ceiling At least 200mm of a free space must be kept above the unit and at least 150mm below the unit Each swimming pool hall is individual thus a special c...

Page 8: ...cular position of the unit and align the unit with the wall 6 4 Securing the position of the unit BACK PLATE SAFETY SCREW HOLES Condensed water is drained from the unit by the force of gravity It is necessary to situate the unit in such a way that there is sufficient declivity for the drainage of condensed water The condensation product must be drained through a siphon into a sewer or into the out...

Page 9: ...ection of the hot water heater element onto the LPHW plumbing is carried out similarly to the installation of radiators On the feeder pipe it is connected by a control valve and on the return pipe by a closing screw joint The LPHW is not supplied with a control valve and a screw joint these are supplied by the supplier of the heating 6 7 LPHW heater element to order Attachment threading of the hot...

Page 10: ...r temperature is checked again and if the current temperature is still below zero a compressor and a ventilator are turned off Gas circuit is reversed and after 3 min a compressor starts System now defreezes the unit for 3 minutes After another 3 minutes if the defrost cycle is completed the unit goes into usual operations In extremely low temperatures and in still humid enough air it is normal to...

Page 11: ... some once a month some once a week Time period in which your filter needs to be cleaned is very much dependent on actual individual conditions in your pool hall It is then required to clean the filter at least once a month Manufacturer distributor or resellers are not responsible for malfunctions damages or failures resulting from not cleaned filter When exchanging the filter power supply to the ...

Page 12: ......

Page 13: ...upposed Connection of the unit to the mains and its protection must correspond with the applicable standards Electrical supply of the unit must be carried out by a protective isolating transformer or it must be protected by a current protective switch with a nominal differential cut off current not exceeding 30 mA At least 1250 mm i e ou SWIMMING POOL The location must be in compliance with the HD...

Page 14: ...66 Exctraction rate at 30 C and 70 RH l 24hrs 43 53 83 Exctraction rate at 30 C and 80 RH l 24hrs 47 5 58 101 Operational temperature standard C 22 35 22 42 22 35 Operational temperature antifreeze stat C 15 35 15 42 15 35 Operational temperature Thermostatic expansive valve TEV C 22 42 22 42 Operational temperature antifreeze stat TEV C 15 42 15 42 Operational temperature hot gas defrost C 5 35 5...

Page 15: ...umidification output Air temperature OUTPUT DIAGRAM OF DEHUMIDIFICATION DRY 500 PLASTIK Air temperature Relative humidity 80 70 60 50 40 80 70 60 50 40 0 10 20 30 40 50 60 15 20 25 30 35 l 24h C 0 20 40 60 80 100 120 15 20 25 30 35 l 24h C OUTPUT DIAGRAM OF DEHUMIDIFICATION DRY 400 PLASTIK Dehumidification output Air temperature Relative humidity 12 ...

Page 16: ...E HEATING WATER MODELS WITH THE LPHW HEATER ELEMENT ONLY THREAD G THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET FROM THE REAR THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET FROM THE REAR THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET FROM THE REAR THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET FROM THE REAR CONDENSATE DRAINAGE FROM THE REAR PIPING WITH MINIMUM INTERNAL DIAMETE...

Page 17: ...L WIRING DIAGRAM OF MODEL MICROWELL DRY 300 400 PLASTIK DRY 300 BASIC Note Producer reserves right to make changes on wiring DRY 300 400 Standard DRY 300 400 EASY 200 HYG 6001 DRY 300 400 LPHW Solenoid Wiring diagram DRY 300 BASIC DRY 300 1 DRY 300 2 14 ...

Page 18: ......

Page 19: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL DRY 300 1 Note Producer reserves right to make changes on wiring 15 ...

Page 20: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL DRY 300 2 Note Producer reserves right to make changes on wiring 16 ...

Page 21: ...IMMING POOL DEHUMIDIFIER USER S MANUAL DRY 300 2 Note Producer reserves right to make changes on wiring L N L L X3 2 1 2 3 4 5 6 7 8 9 10 C external thermostat Solenoid valve 230V AC 50Hz Power Supply Box Brown Red 17 ...

Page 22: ... S MANUAL WIRING DIAGRAM OF MODEL MICROWELL DRY 500 PLASTIK DRY 500 BASIC Note Producer reserves right to make changes on wiring DRY 500 Standard DRY 500 EASY 200 HYG 6001 DRY 500 LPHW Solenoid Wiring diagram DRY 500 BASIC DRY 500 1 DRY 500 2 18 ...

Page 23: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL Note Producer reserves right to make changes on wiring DRY 500 1 19 ...

Page 24: ......

Page 25: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL Note Producer reserves right to make changes on wiring DRY 500 2 20 ...

Page 26: ...WALL MOUNTED SWIMMING POOL DEHUMIDIFIER USER S MANUAL 21 ...

Page 27: ...pe d6mm 1 20 Screw ST4 8 x 38 2 21 Screw 3 5 x 13 9 24 Rubber grommet d15 DA 110 150 10 4 25 Rubber grommet d30 DA 230 300 20 4 26 Condensate pipe d18x3 1m 1 Position Component Number of pieces 1 Fiberglass cover 1 1 1 Inlet grid SMH2 20 1005 x 65 1 1 2 Outlet grid SMH2 12 5 1075 x 65 1 2 Back metal sheet 1 3 Metal sheet in front of the exchanger 1 4 Metal sheet above the exchanger 1 5 Metal sheet...

Page 28: ... 50 Ozone ppm 0 8 1 0 Maximum copper content ppm max 2 Aquamatic single purifier ppm max 2 Tarn clean purifier ppm max 2 Sherwood purifier ppm max 2 TRANSPORT INSTRUCTIONS The dehumidifiers must be transported only in the original packaging and in a vertical position Make sure that the dehumidifier cannot turn over or fall down during transportation Do never put the dehumidifier aside It may lead ...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...MICROWELL spol s r o SNP 2018 42 927 01 Šaľa Slovakia Phone 421 31 7020 540 1 Fax 421 31 7020 542 E mail microwell microwell sk www microwell eu Distributed by VERSION 2017 04 24 ...

Page 33: ...Е ТАКЖЕ Осушители воздуха Кондиционеры сплит системы Вытяжные вентиляторы Бытовые рекуператоры Увлажнители воздуха Очистители воздуха Метеостанции Барометры Аксессуары для микроклимата Бактерицидные облучатели ...

Reviews: