A.
Electrical installation FRESH AIR INTAKE WITH AUTOMATIC CONTROL
OF BLINDS
FRESH AIR INTAKE
(automatic fins)
WASTE AIR EXHAUST
(automatic fins)
MAIN POWER SUPPLY
OF DEHUMIDIFIER
230V/50Hz/1f
3x 2.5mm
2
CYSY
breaker
16A(DRY800)/20A
(DRY1200) type C
circuit breaker 30mA
PERIPHREAL CONTROL
230V/50Hz/1f
3x 0.5-1mm
2
CYSY
Separate contactor with separate phase
The contactor is supplied by the
customer (fan and electric blinds are
part of the delivery if ordered)
Electric
fins
Electric
fins
External
fan