alarm_record_faulthi
1)
The "Fault alarm" is recorded in the alarm list (read only).
alarm_tx_alarmlo
1)
An immediate transmission is initiated in the event of a "Warning".
alarm_tx_alarmhi
1)
An immediate transmission is initiated in the event of an "Alarm" (read only).
alarm_tx_faultlo
1)
An immediate transmission is initiated in the event of a "Fault warning".
alarm_tx_faulthi
1)
An immediate transmission is initiated in the event of a "Fault alarm".
alarm_quick_alarmlo
1)
The "Record interval on event" is used in the event of a "Warning".
alarm_quick_alarmhi
1)
The "Record interval on event" is used in the event of an "Alarm".
alarm_quick_faultlo
1)
The "Record interval on event" is used in the event of a "Fault warning".
alarm_quick_faulthi
1)
The "Record interval on event" is used in the event of a "Fault alarm".
fault1 - fault4
Procedure in the event of measurement range violations (only for channels in "0-20 mA" or
"4-20 mA" mode)
Value
Explanation
0
Ignore
The measurement value is calculated beyond the range limits.
1
Silent
cutoff
The measurement value is truncated at the range limits.
2
Out of
range
4-20 mA
l
The error value "OL" (open loop) is issued, if the
measurement value is below 3.9mA.
l
If the measurement value is above 20.1 mA, the
error value "SC" (short circuit) is issued.
0-20 mA
l
If the measurement value is above 20.1 mA, the
error value "SC" (short circuit) is issued.
3
NAMUR
borders
4-20 mA
l
The error value "OL" (open loop) is issued, if the
measurement value is below 3.6mA.
l
The error value "UF" (underflow) is issued, if the
measurement value is below 3.9mA.
l
The error value "OF" (overflow) is issued, if the
measurement value is above 20.1mA.
l
If the measurement value is above 21mA, the error
value "SC" (short circuit) is issued.
0-20 mA
l
The error value "OF" (overflow) is issued, if the
measurement value is above 20.1mA.
l
If the measurement value is above 21mA, the error
value "SC" (short circuit) is issued.
88