background image

Programming by keyboard or by RS485

  

    

1. Sensor and input signal selection:

Variant 1

 – RTD or TC selection with linearization in the device. 

Linearization is up to 9

th

 stage in 4 sub-ranges. In RTD it is necessary its connection to be selected

In TC it is necessary the automatic correction of the cold end to be enabled or disabled. The 
dimension have to be set - º C or º F.
The sensor range is set by parameters. 

Variant 2

 – The input signal is linear current or voltage.

The transmitter range is set by parameters

Variant 3

 – The sensor is non-standard nonlinear – it can be linearized by request or by the user by 

RS485, MODBUS RTU protocol, by entering polynomial up to degree three coefficients. 

Variant 4

 -  At sensor/transmitters with unknown transmission characteristics it is possible to be set 

linear by two points by physical change of the technological quantity and setting of two limit values 
in the device.  

2. Setting of decimal point and lower and upper limit of the range,  set-points parameters, alarms,

bargraph etc.  

3. Selection of analogue output and range setting – if it is available / ordered /.
4. System setting of analogue inputs – if it is necessary.
5. System setting of analogue outputs – if it is necessary.

 

6. Setting of communication parameters – if RS485 is available.

*  

It is possible to begin with this procedure

To restore the factory settings – page 20

After changing the decimal point all the parameters related with PV – process variable, 
influencing on the range, bargraph, set-points etc. have to be changed 

For controller programming Microsyst offers:

USB / RS485 Convertor

Base software for setting for operating systems Windows

MOST COMMONLY USED ABBREVIATIONS:

RTD - resistance temperature detector

TC

- thermocouple

ATC - automatic temperature correction 

PV

- process variable

SP

- set point – set point for regulating of the measured process variable 

OFFSET- offsetting the indication of input or output value

Aout - analog output

Document revision 2015-03-20

2

Summary of Contents for MS6026

Page 1: ...COMPETENCE IN MEASUREMENT Process Meter with Tricolor Bargraph and Universal Input MS6026 MS6126 v 2 2 USER MANUAL PLOVDIV 2015 Document revision 2015 03 20...

Page 2: ...wo limit values in the device 2 Setting of decimal point and lower and upper limit of the range set points parameters alarms bargraph etc 3 Selection of analogue output and range setting if it is avai...

Page 3: ...UT OFFSET 18 XI RECOMMENDATIONS AGAINST INTERFERENCE 19 XII ANALOG INPUTS SETTING SERVICE SETTING LINEAR INPUT SETTING BY TWO REFERENCE POINTS SETTING OF NON STANDARD INPUT 19 19 20 20 XIII RESTORING...

Page 4: ...Measurement accuracy 0 1 from range for 0 10V DC and 0 20 mA Time to refresh 0 5 sec Lower and upper limit NAMUR level detection 1 56 105 4 from the range i e for 4 20 mA 3 75 20 86 mA Auxiliary power...

Page 5: ...0 92 6 1950 24 0 15 0 04 Pt1000_385 EN 60751 200 850 185 2 3904 8 0 15 0 04 Pt100_391 GOST 200 850 17 24 395 16 0 15 0 04 Pt100_392 JIS C1604 81 200 660 17 08 337 03 0 15 0 04 Cu100_482 GOST 180 260 2...

Page 6: ...31 types of sensors 6 of which customer adjustable Universal power supply 90 250 VAC Tricolor bargraph 7 zones that can be configured by the customer as levels and color green red or orange Five digi...

Page 7: ...VI FRONT PANEL AND TERMINALS MS62026 Document revision 2015 03 20 7...

Page 8: ...N OF INPUTS AND OUTPUTS POWER SUPPLY Terminals 14 15 DIGITAL OUTPUTS Designation Model MS6026 MS6126 Contacts NO NO COM NC Outputs and Terminals 1 3 4 4 5 6 2 5 6 7 8 9 K3 7 8 10 11 12 K4 9 10 K5 11 1...

Page 9: ...input Positive terminal Iin PAS 25 Negative terminal Iin PAS 24 Voltage input 0 000 10 000 V Positive terminal U in 23 Negative terminal U in 24 Voltage input 0 000 1 000 V Positive terminal TC 29 Neg...

Page 10: ...t for MS6126 Alarm output K5 of MS6026 is identical to K3 of MS6126 Possible non standard versions in which K3 of MS8126 to realized as a control with hysteresis SP3 SP2 SP1 K3 K2 K1 3 3 1 1 SP4 K4 4...

Page 11: ...er Syst GC By SySt GP parameter the mode lighting column lighting point is determined When a LED is between two color zones when changing PV it would change its color thereby slightly expands one zone...

Page 12: ...rom parameters menu should not be in value change Press and hold this button for 4 sec while v 1_5 appears on the display V 1_5 is the software version of the device 2 minutes after the last pressed b...

Page 13: ...it is necessary points of AH and AL are automatically exchanged at rnGL rnGH 57 Uint 1 Hysteresis at 1 4 outputs operation A negative value inverts the corresponding output 1999 9999 Dimension as PV H...

Page 14: ...es if Syst Et 0 0 1V 0 10V 4 20mA and 0 20mA rnGL Measurement range lower limit Indication for 0V 0mA 4mA if Syst Et 0 1999 9999 Dimension as PV 20 Sint rnGH Measurement range upper limit Indication f...

Page 15: ...on linear input setting by two reference points If changed the current setting will remain valid until such new Et 1 or until range correction rnGL rnGH Et 0 BackUp options For Input Output settings a...

Page 16: ...tory set This setting scales the analog outputs to correspond to 0 20 mA and 0 10 V This requires an reference mA meter or V meter with accuracy higher than 0 1 to be connected to the respective outpu...

Page 17: ...s of the device 1 255 MODBUS HOLD REG ADDRESS 127 Uint 1 1 ConF System settings Field 1u indicates analog type used hardware related Field rr Normal Mode Rejection Ratio BAUDRATE PARITY STOP BIT are c...

Page 18: ...reviations Uint UNSIGNED INT Sint SIGNED INTEGER X OFFSET OF THE ANALOG INPUT CodE 47 In this mode can be entered value which will be added when measuring the input parameter offset if there is dispar...

Page 19: ...ly change of the input parameter but ignores short disturbances 3 Programming of Normal Mode Rejection Ratio NMRR filter Depending on the frequency of the power supply it is desirable to select approp...

Page 20: ...be entered in the lower range limit rnGL about 0 03 of the range For the range 1 V the optimum settings are made in range 0 1V non standard 1 SETTING OF LINEAR INPUT BY TWO REFERENCE POINTS CodE 80 T...

Page 21: ...be connected up to 32 devices with repeaters up to 247 There is an option for a special performance for up to 128 devices without repeaters In the parameters table in column HOLDING REGISTER ADDRESS a...

Page 22: ...LIBRATION COEFFICIENTS HOLDING REG ADR 512 524 626 628 TYPE FLOAT 4 BYTE IEEE754 RSP3 512 RSP2 514 RSP1 516 RSP0 518 Polynomial calibration coefficients Non standard input Convert normalized linear in...

Page 23: ...et 630 K_C4 K_C3 The device memory is RAM and non volatile Grey fields are part from RAM memory In power supply failure and restoring the power supply this quantities initialize equate their values fr...

Page 24: ...sport poor storage incorrect usage forces of nature failure to follow instructions and when others made an attempt to remove the defects In these cases the defect can only be removed for a fee Service...

Reviews: