The D12 adapter shaft of the pms
sensor has to stick out at least 
6 mm from the screw connection
(see figure 5).

The sealing ring has to fill space
between D12 sensor shaft and cap
nut. Sealing ring should not to be
pressed out excessively from the
shaft gland.

Fig. 3:  pms sensor D12-adapter shaft with 

sensor screw connection BF-pms/A1, 

all surfaces must be inclined at least 3°.

min. 

Fig. 4:  Mounting of pms sensor with sensor 

        screw connection BF-pms/A1

Fig. 5:  Mounting of pms sensor with sensor  

        screw connection BF-pms/A1

Mounting accessory

D12 sensor screw connection

    BF-pms/A1

Accessory for programming

LinkControl adapter LCA-2

Adapter 5G/M12-4G/M12/M8

6

min. 

The pms sensors are IO-Link-capable
in accordance with IO-Link specifica-
tion V1.1.

Note

In IO-Link mode LinkControl and syn-
chronization via pin 2 are not
available.

Smart Sensor Profile

Die pms sensors support the Smart
Sensor Profile. The following profiles
and function classes are integrated:

0x000A - Device Profil: 
Digital measuring sensors

0x8000 - Device Identification

0x8001 - Multichannel: 
two setpoint switching sensor

0x8003 - Device Diagnosis

0x8004 - Teach Channel

0x800A - Measurement Data Cha-
nel (standard resolution)

Synchronisation in IO-Link Mode

In IO-Link mode each sensor is syn-
chronized on the protocol of the IO-
Link master. In multiple sensor opera-

tion the sensors are synchronous if
the master protocols are synchro-
nous.

System Commands

With 3 system commands the follo-
wing settings may be carried out:

Teach-in SP1

Teach-in SP2

Reset sensor to factory settings

SSC1 Configuration

The pms sensor has 5 modes:

Single point (SP1: switching point)
The switched output is activated
when the distance to an object is
under that of the present single
point SP1.

Window (SP1, SP2: window mode)
The switched output is set when
the object is within the set win-
dow  (SP1, SP2). 

Two point (SP1, SP2: hystese
mode)
In hysteresis mode, SP1 and SP2
assume the function of the single
point and return single point.

Single point +8 % (SP1 switching
point +8 %) 
The switched output is set when
the distance mesaured to an ob-
ject is smaller that the set swit-
ching point  SP1 +8%.

Window ±8 % (SP1 two way re-
flective barrier)
The switched output is set when
the object is between sensor and
fixed reflector (with SP1 ±8 %) .

IODD File

The  latest  IODD  file you will find
on the internet under

www.microsonic.de/en/IODD

.

For further informations on IO-Link
see 

www.io-link.com

.

IO-Link data

Physical layer

SIO mode support

min cycle time

yes
8 ms

baud rate

format of process data

COM 2 (38.400 Bd)
Frametype 2_V, 4 Byte

Identification features

content of process data

Bit 0: state of switched output, Bit 8-15: scale (Int. 8),
Bit 16-31: measured value (Int. 16) with 0,1 mm resolution

Vendor name

microsonic GmbH

Vendor ID

Product name

419 (0x01A3)
pms-15/CF/A1

Product ID

Device ID

35000
29 (0x00001D)

SSC1 configuration

Parameter

index

SP1 (Setpoint 1)
SP2 (Setpoint 2)

60
60

SSC1 configuration

Hysterese

61

Logic 

index

61

Teach-in

Mode

Teach-in channel

61
58

Teach-in status

SP1 single value teach-in

59
2

Filter

Temperature compensation

SP2 single value teach-in

Type

2
256

Strength

 Mode

256
300

Factory settings

FactorySettings

DeviceaccessLocks

2
12

1) Distance value, e.g. setpoints, are give with a resolutin of 0,1 mm. The values in the tables are decimal.

subindex format

1
2

INT16
INT16

access

range

R/W
R/W

20 - 250 

1)

20 - 250 

1)

3

INT8

subindex

1

format

UINT16

R/W

0,1 - 230 

1)

access

R/W

range

0: High active, 1: Low active

2

UINT8
UINT8
UINT8
UINT8

R/W
R/W

1: single point (SP1: switching point), 2: window (SP1, SP2: window mode), 3: two point (SP1, SP2: hysteresis mode), 128: single point +8 % (SP1: switching point +8 %), 129: window ±8 % (SP1: two way reflective barrier)
0: SSC1: Pin 4 (Push-Pull)

RO
WO

Bit 0-3: 0: idle, 1: SP1 success, 2: SP2 success, 7: error; Bit 4: SP1 TP1; Bit 6: SP2 TP1
65: The value 65 must be written to index 2 to trigger the command.

UINT8
UINT8

1

UINT8
UINT8

WO
R/W

66: The value 66 must be written to index 2 to trigger the command.
0-4: F00 (no filter), F01 (standard filter), F02 (averaging filter), F03 (foreground ilter), F04 (background filter)

R/W
R/W

0-9: P00 - P09; For each measurement filter a filter strength between 0, weak filter effect, and 9, strong filter effect, can be chosen.
0: off, 1: on

UINT8
UINT16

WO
R/W

130: The value130 must be written to index 2 to trigger the command.
Bit 0: parameter (write) access lock; Bit 2: local user interface lock

yes
8 ms
COM 2 (38.400 Bd)
Frametype 2_V, 4 Byte

yes
16 ms
COM 2 (38.400 Bd)
Frametype 2_V, 4 Byte

Bit 0: state of switched output, Bit 8-15: scale (Int. 8),
Bit 16-31: measured value (Int. 16) with 0,1 mm resolution

microsonic GmbH
419 (0x01A3)
pms-25/CF/A1
35100
30 (0x00001E)

Bit 0: state of switched output, Bit 8-15: scale (Int. 8),
Bit 16-31: measured value (Int. 16) with 0,1 mm resolution

microsonic GmbH
419 (0x01A3)
pms-35/CF/A1
35200
31 (0x00001F)

index subindex

60
60

1
2

format access

UINT16
UINT16

R/W
R/W

61

3

UINT8

R/W

range

index

30 - 350 

1)

30 - 350 

1)

60
60

subindex format

1
2

UINT16
UINT16

0,1 - 320 

1)

61

3

UINT8

yes
20 ms
COM 2 (38.400 Bd)
Frametype 2_V, 4 Byte
Bit 0: state of switched output, Bit 8-15: scale (Int. 8),
Bit 16-31: measured value (Int. 16) with 0,1 mm resolution

microsonic GmbH
419 (0x01A3)
pms-100/CF/A1
35300
32 (0x000020)

access range

R/W
R/W

65 - 600 

1)

65 - 600 

1)

index subindex

60
60

1
2

R/W

0,1 - 535 

1)

61

3

format access

UINT16
UINT16

R/W
R/W

range

120 - 1300 

1)

120 - 1300 

1)

UINT8

R/W

0,1 - 1180 

1)

pms-15...

pms-25...

pms-35...

pms-100...

IO-Link mode

microsonic GmbH / Phoenixseestraße 7 / 44263 Dortmund / Germany / 

T

 +49 231 975151-0 / 

F

 +49 231 975151-51 / 