Output voltage and current limit adjustment

The   output   voltage   and   output   current   limit   of   the   power   supply   can   be   adjusted   as   using   the   multi-turn
potentiometers accessible from the front panel.

Both voltage and current can be adjusted from zero to the maximum value. Maximum 800W output power is
available within the adjustment range.

The power supply includes 16 pre-programmed output voltages that are set by the code switch. See the setting
table for this unit. Any of these 16 different voltage settings can be taken in use and additionally be adjusted within
±5% using the trimmer on the front panel. See the instructions for choosing the programmed voltage and the fine-
tune adjustment.

LED

An orange LED indicates a healthy power supply output voltage.

Overcurrent protection

The output of the power supply is protected against overcurrents and short circuits by an automatic, self-resetting
electronic current limiter.

Series/parallel connection

Parallel operation: No restrictions, passive load sharing
Series operation:  Series operation: Up to 500V total voltage.   For more information about use with an AI or S
option, ask the manufacturer. 

Warning

Dangerous voltages, capable of causing death are present in the power supply. Do not remove the cover. There 
are no operator serviceable parts inside the unit. Refer servicing to qualified service personnel only.

Modular connectors

STATUS

POWERFINN OY (LTD)

www.powerfinn.fi

J8

J5

J6

N O T   F O R   T E L E P H O N E   U S E

C L A S S   2

S e e   m a n u a l   f o r   c o n n e c t i o n s

Front panel

The programming switch is situated left from the 
status LED.

Rear panel

J8

Alternatively power failure alarm relay

J5

Temperature compensation (Temp.comp models);
Voltage drop compensation option

J6

Optional external LED

Alarm relay (Option R)

On models with an alarm relay, the alarm relay output indicates whether the output voltage is healthy or not. The
alarm signal is activated in case of an AC failure or charger failure. Both normally closed signals and normally
open contacts are available.

Pin configuration, modular connector J8 with alarm relay option